DESIGN STRATEGIES FOR CLIMATE TYPES
HOT-ARID CLIMATE
THICK WALLS
THERMAL MASS
SHADE
SMALL WINDOWS
WATER FEATURES
COURTYARDS
LOW-E WINDOWS
BOTTOM OF A VALLEY
SOUTH OF A POND
HOT-HUMID CLIMATE
LARGE OPENINGS FOR BREEZES
LONG EAST-WEST DIMENSIONS
ORIENTATION TO BREEZES
TALL CEILINGS
CEILING FANS
SPRAWLING BUILDING FORM
TOP OF A HILL
SOUTH OF A POND
TEMPERATE CLIMATE
LONG EAST-WEST DIMENSION
INSULATION
SOUTH FACING WINDOWS
BUFFERS FOR WINTER WINDS
MINIMIZE NORTH FACE OF BUILDING
MAXIMIZE SOUTH FACE OF BUILDING
DECIDUOUS TREES ON SOUTH SIDE OF BUILDING
¾ OF THE WAY UP A HILL
COLD CLIMATE
COMPACT BUILDING FORM TO MINIMIZE HEAT LOSS
SLIGHTER LONGER IN THE EAST-WEST DIRECTION
INSULATION
LOW U-VALUE WINDOWS
MEASURE OF HOW MUCH HEAT TRANSFERRED THROUGH THE WINDOW
AIR TIGHTNESS
EVERGREEN TREES ON THE WINDY SIDE OF THE BUILDING AS BUFFER
¼ OF WAY UP A HILL
NORTH SIDE OF A POND
THERMAL
FOR A SOUTH FACING WINDOW (TEMPERATE CLIMATE, NORTHERN HEMISPHERE) WHICH BUILDING TYPE WOULD BENEFIT MORE FROM THE USE OF GLASS WITH A HIGHER SOLAR HEAT GAIN COEFFICIENT (SHGC)? A SKIN-LOAD-DOMINATED BUILDING OR AN INTERNAL-LOAD-DOMINATED BUILDING?
A SKIN-LOAD-DOMINATED BUILDING
SKIN-LOAD-DOMINATED BUILDINGS
HAVE A LOT OF SURFACE AREA RELATIVE TO THEIR VOLUME, SO INFLUENCED HEAVILY BY THE CONDITIONS OUTSIDE
INTERNAL-LOAD-DOMINATED BUILDINGS
IE SMALL OFFICE BUILDINGS, THEATERS, BIG HOSPITALS, ETC
0 < (SHGC) < 1
HIGH SHGC IS TYP AROUND 0.7 TO 0.9
LOW SHGC IS TYP AROUND 0.2 TO 0.4
LOW-E WINDOWS
BOAST LOW HEAT GAIN
IDEAL FOR HOT CLIMATES
LOW-U VALUE
BOASTS BETTER INSULATION
IDEAL FOR COLD CLIMATES
SOLAR INSOLATION
AMOUNT OF HEAT COMING THROUGH
HIGH SOLAR HEAT ON THE SOUTH TO WARM UP THAT CONCRETE MASS (FLOOR)
LOW SOLAR HEAT GAIN ON THE NORTH
GLAZING
LOW E GLASS LETS LESS HEAT COME INTO A ROOM FROM THE SUNLIGHT
DESIRABLE IN HOT CLIMATE AREAS
LOW U GLASS LETS LESS HEAT BE TRANSMITTED OUT FROM INSIDE OF A ROOM
DESIRABLE IN COLD CLIMATE AREAS
BTU’S
HOW MANY BTU’S ARE REQUIRED TO MOVE 1 POUND OF WATER FROM 70 TO 71 DEGREES FAHRENHEIT?
1
HOW MANY BTU’S ARE REQUIRED TO MOVE 2 POUNDS OF WATER FROM 70 TO 71 DEGREES FAHRENHEIT?
2
HOW MANY BTU’S ARE REQUIRED TO MOVE 2 POUNDS OF WATER FROM 70 TO 72 DEGREES FAHRENHEIT?
4
HOW MANY BTU’S ARE REQUIRED TO MOVE 1 POUNDS OF WATER FROM 72 TO 212 DEGREES FAHRENHEIT?
212 - 72 = 140 BTU’S
HOW MANY BTU’S ARE REQUIRED TO MOVE 1 POUNDS OF WATER FROM 212 DEGREES WATER TO 212 DEGREES STEAM?
1061 BTU’S
HUMIDITY
YOU ACTUALLY SWEAT MORE WHEN IT IS DRY NOT WHEN IT IS HUMID
THE DRY AIR ALLOWS FOR THE SWEAT TO EVAPORATE OFF YOUR SKIN
WHEN THINGS EVAPORATE THEY MAKE EVERYTHING AROUND THEM COLD
WARMER AIR CAN HOLD MORE MOISTURE
COOLER AIR CAN’T HOLD AS MUCH AND RESULTS IN DEW
LOW-E GLASS
BOASTS A LOW SOLAR HEAT GAIN COEFFICIENT
CLIMATE
A LOCALE THAT GENERALLY HAS COOL SUMMERS IS LIKELY TO HAVE FEW COOLING DEGREE DAYS
TEMPERATE CLIMATE
FOR A TEMPERATE CLIMATE (WARM SUMMERS AND COLD WINTERS), HEAT TRANSFER FOR CONDUCTION (Q) IS MORE OF A CONCERN FOR WINTER AS OPPOSED TO SUMMER BECAUSE THE DELTA T’S ARE HIGHER
CONDUCTION IS A BIGGER DEAL IN THE WINTER
LATENT HEAT GAINS AND SOLAR HEAT GAINS BECAUSE A BIG DEAL IN THE SUMMERS
INSULATION
R VALUE OF 10 IS MOST APPROPRIATE FOR AN INSULATING MATERIAL
HVAC
HVAC (HEATING, VENTILATION, AIR CONDITIONING)
HEATING/COOLING
EVAPORATION AND CONDENSATION
LIQUID TO GAS
REQUIRES A LOT OF HEAT TO CHANGE LIQUID TO GAS (EVAPORATION)
REVERSE OF THAT
WE PRODUCE HEAT WHEN WE GO FROM GAS TO LIQUID (CONDENSATION)
COOLANT THAT IS
EVAPORATING OR BOILING IS COOL
CONDENSING IS WARM
BOILING POINT OF A FLUID
FUNCTION OF PRESSURE (AS WELL AS TEMPERATURE)
LOW PRESSURE INDUCES BOILING
PULLING APART DENSER LIQUID MOLECULES AND THUS CHANGES THEIR STATE TO A GAS
HIGH PRESSURE INDUCES CONDENSATION
COMPRESSING THE GAS MOLECULES INTO A DENSER LIQUID
BOILING AND CONDENSING
ACCOMPLISHED BY PRESSURIZING AND DEPRESSURIZING THE COOLANT
COOLING
AIR HANDLING UNIT HAS A LONGER DUCT RUN THAN A FAN COIL UNIT
A FAN COIL UNIT IS ESSENTIALLY A FAN IN THE ROOM
AC (AIR CONDITIONING)
IN THE COMPRESSION-REFRIGERATION LOOP (AIR CONDITIONING), WHICH IS LIKELY TO BE WARMER: CONDENSER COIL OR EVAPORATOR COIL?
CONDENSER COIL
HEAT PUMP
CAN EITHER HEAT OR COOL
JUST NEEDS TO REVERSE THE DIRECTION OF THE FLOW OF THE COOLANT, THE PUMP THAT MOVES THE REFRIGERANT AROUND IN THE CYCLE
PLUMBING
UNDERGROUND PIPE
TYPE K
ORDER OF THICKNESS OF PIPE
TYPE K: THICKEST
TYPE L: MEDIUM (MOST COMMON FOR SUPPLY LINES)
TYPE M: THINNER (MIGHT TAKE CONDENSATION FROM EVAP COIL)
TYPE DWV
STACK VENT UTILIZES WHICH PIPE?
TYPE DWV
FOR DRAINAGE AND VENTS
SUPPLY AND WASTEWATER
NEVER MEET
VIA AIR GAP
BACKFLOW PREVENTER
WATER RUNS ONE WAY, SHOULD WATER BACK UP, INSTEAD OF PULLING FROM THE WATER, A MECHANISM MAKES IT SO AIR FILLS THE PIPE
VALVES
GATE VALVE: MOSTLY USED FOR MAINTENANCE
GLOBE VALVE: MOSTLY USED FOR FAUCETS, REPEATED USE
CHECK VALVE: USED FOR BACKFLOW PREVENTION
WATER PRESSURE
P (PRESSURE) = 0.433 (CONSTANT x HEIGHT)
FOR 75 FEET, WATER PRESSURE = 32 PSI (75 x 0.433)
MIN PRESSURE FOR FIXTURES RANGES BETWEEN 4 PSI TO 20 PSI
WATER MAIN TYP 50 PSI BUT CAN ALSO BE UP TO 70 PSI
WATER GRAPHICS FOR DRAWINGS/DIAGRAMS
PLUMBING SUPPLY LINE FOR COLD WATER: LONG DASH ONE DOT LONG DASH ONE DOT LONG DASH ONE DOT
PLUMBING SUPPLY LINE FOR HOT WATER: LONG DASH TWO DOTS LONG DASH TWO DOTS LONG DASH TWO DOTS
PLUMBING SUPPLY LINE FOR CONVECTIVE LOOP: LONG DASH THREE DOTS LONG DASH THREE DOTS LONG DASH THREE DOTS
CONVECTIVE LOOP
ALWAYS MAINTAINS WARM WATER THROUGHOUT THE BUILDING SO WHEN YOU TURN ON HOT WATER, IT'S NOT HOT INSTANTANEOUSLY BUT ITS NOT COLD EITHER, IT'S SORT OF WARM
WATER WASTE
BLACK WATER
INVOLVES HUMAN WASTE OR FOOD WASTE IE KITCHEN SINK OR TOILET
GRAY WATER DOES NOT INCLUDE HUMAN WASTE OR FOOD WASTE
LAVATORIES, WASHING MACHINES, SHOWERS
HARD WATER
MINERALS IN WATER THAT CLOG UP PIPING
INSULATE PIPES
TO KEEP HEAT OR COOLTH OVER LONG DISTANCES
INSULATE COLD WATER PIPES
ELECTRICITY (EDISON VS TESLA STORY BELOW IN GREY)
EDISON (DIRECT CURRENT) VS TESLA (ALTERNATING CURRENT)
END OF 1800’S THOMAS EDISON WAS ESTABLISHED
& TESLA FROM A YOUNGER GENERATION WAS JUST AS BRILLIANT AND HARD WORKING LESS OF A SHOWMAN, KIND OF AWKWARD, ETC
HAD SOME KIND OF OCD WHERE HE HAD TO DO EVERYTHING IN FACTORS OF THREE
TESLA COMES TO WORK FOR EDISON THROUGH SOME SORT OF A REFERRAL
TESLA CONTINUALLY TRIES TALKING EDISON INTO MOVING TOWARDS ALTERNATING CURRENT
EDISON WHO OWNS ALL THE PATENTS ON DIRECT CURRENT PREFERS TO IGNORE TESLA
AT ONE POINT THEIR CONFLICTING STYLES COME TO A HEAD
EDISON PROMISED TESLA $50K IF HE COULD SOLVE AN ENGINEERING PROBLEM THAT HE HAD, WHICH HE DID, AND THEN WAS NOT GIVEN THE $50K
SO HE QUIT
EDISON WAS A FAMOUS INVENTOR BUT HE WANTED TO EVOLVE INTO A CAPTAIN OF INDUSTRY SORT OF LIKE STEVE JOBS
TESLA IS INTRODUCED TO GEORGE WESTINGHOUSE EVENTUALLY
TESLA EXPLAINS TO WESTINGHOUSE THE ADVANTAGES OF ALTERNATING CURRENT
WESTING GETS ON BOARD AND THEY GO UP AGAINST EDISON
EVENTUALLY ALTERNATING CURRENT WON
BATTERY & MORE
PRODUCES VOLTAGE (OR PRESSURE)
IN EDISON'S DAY THEY CALLED VOLTAGE ELECTRICAL PRESSURE
VOLTAGE SENDS ELECTRICITY THROUGH WIRING AS CURRENT
CURRENT IS EQUIVALENT TO PIPE SIZE (SIMILAR TO WATER FLOW)
BIGGER WIRE WILL CARRY MORE CURRENT
WHICH GOES AGAINST A RESISTOR IE A LAMP
THERE IS A SWITCH THAT WHEN IT IS CONNECTED IT CONNECTS A CIRCUIT
ELECTRICITY IS THE MOVEMENT OF FREE ELECTRONS IN A MEDIUM
IT'S THE MOVEMENT THAT MAKES THE WHOLE THING WORK
WHAT KIND OF MATERIALS HAVE A LOT OF FREE ELECTRONS?
METALS
DIRECT CURRENT
POSITIVE AND NEGATIVE END OF BATTERY
WHICH GOES THROUGH A CONDUCTOR
CONDUCTOR IS OFTEN WRAPPED IN AN INSULATOR
AND THEN GO THROUGH A RESISTOR LIKE A LIGHT BULB OR LAMP
AND IT WILL COME BACK
THE ELECTRONS WILL MOVE THROUGH THE CONDUCTOR, ACROSS THE RESISTOR (LIGHT BULB), THE BULB WILL LIGHT UP, AND IT WILL RETURN, AND EVENTUALLY THE PRESSURE AT THE POSITIVE AND NEGATIVE ENDS AT THE BATTERY WILL BE EVEN
ALTERNATING CURRENT
WE ARE TAKING A POWER SOURCE, MOVING IT ACROSS THE RESISTOR BACK AND FORTH
IN THE US WE MOVE IT BACK AND FORTH 60 TIMES PER SECOND
PARTS OF EUROPE IT IS 50 TIMES PER SECOND
THAT IS WHY YOU NEED AN ADAPTOR
OHMS LAW
W (POWER IN WATTS) = I (CURRENT IN AMPS) x V (VOLTAGE IN VOLTS)
W: LIKE GALLONS PER MINUTE COMING OUT OF THE HOSE
I: SIZE OF THE HOSE
V: PRESSURE OF THE HOSE
CRUCKS OF WHY TESLA’S ALTERNATING CURRENT WON
WHEN YOU RUN HIGH VOLTAGES YOU NEED TO BE ABLE TO STEP THEM DOWN
START AT POWER PLANT AND PRODUCE SAY 60,000 VOLTS (COULD BE HIGHER)
REGIONAL FEEDERS OF HIGH VOLTAGE TRANSMISSION LINES THAT LOOK LIKE GIANT ERECTOR SETS AND DOT THE LANDSCAPE HIGH OFF THE GROUND
THEY ARE HIGH OFF THE GROUND BECAUSE WE DON'T WANT THE POWERS TO ARC
BECAUSE THEY ARE LIVE
BIRDS CAN REST ON THEM BECAUSE THEY ARE NOT TOUCHING THE GROUND AND THEY DON'T HAVE THE BEST PATH FOR THE ELECTRONS TO GO THROUGH BUT IF IT WAS A SQUIRREL THE SQUIRREL COULD GET ZAPPED IF HE PRODUCES A BETTER PATH FOR THE ELECTRONS TO MAKE THEIR WAY TO THE GROUND IE THE TAIL TOUCHES THE WIRE AND THE NOSE TOUCHES THE POLE THAT SUPPORTS IT
THE VOLTS MOVE ACROSS THE COUNTRY FROM THE POWER PLANT TO POWER SUBSTATIONS
SUBSTATIONS STEP VOLTAGE DOWN FROM IE 60,000 TO SAY 12,000
IT THEN RUNS ON WOODEN POLES THROUGHOUT THE CITY UNTIL IT REACHES THE BUILDINGS
AT THE BUILDING THERE IS ANOTHER TRANSFORMER THAT TRANSFORMS THE 12,000V TO 120V
TESLA’S ALT CURRENT WON BECAUSE AT THE TIME, WE WERE NOT ABLE TO STEP DOWN THE DIRECT CURRENT
AT THE TIME, WE DIDN'T HAVE THE EQUIPMENT TO STEP DOWN VOLTAGE, WE DIDN'T HAVE TRANSFORMERS THAT WORKED W DIRECT CURRENT, ONLY WITH ALT CURRENT
THERE WOULD NEED TO BE A POWER PLANT IE A SMALL GENERATOR EVERY FEW BLOCKS
BECAUSE WE COULDN'T TAKE DIRECT CURRENT TOO FAR
BECAUSE IF WE TRIED TO DO SO
WE WOULD NEED TOO MUCH WATTAGE
IF WE NEED TOO MUCH WATTAGE, WE NEED BIGGER PIPES, WHICH MEANS WE NEED MORE AMPERAGE
IF WE NEED MORE AMPERAGE OVER LONG DISTANCES
WE HAVE TOO MUCH HEAT BUILD UP AND TOO MUCH ELECTRICITY LOST TO ELECTROMAGNETISM IN THE TRANSMISSION
SO, IN EDISON’S MODE, IT WAS A DISTRIBUTED MODEL WHERE THERE WERE POWER PLANTS KIND OF EVERYWHERE
WITH TESLA’S MODEL, YOU COULD PUT REMOTE POWER PLANTS
WHEN/WHERE DIRECT CURRENT IS STILL USED
UNDERWATER: IF WE ARE TRYING TO TIE GREAT BRITAIN TO MAINLAND EUROPE
GROUND IS NEUTRAL
HOT WIRE TAKES POWER FROM THE POWER PLANT
AND THOSE ELECTRONS ARE MOVING BACK AND FORTH
AND THERE IS A NEUTRAL WIRE
IF THE CIRCUIT IS CONNECTED
THE ELECTRONS IN THE NEUTRAL WIRE ARE ALSO MOVING BACK AND FORTH
THE NEUTRAL WIRE IS GROUNDED, IT DOESN’T GO BACK TO THE POWER PLANT
PUTTING ELECTRONS INTO THE GROUND AND TAKING THEM OUT, PUTTING IN AND TAKING OUT
CAPACITORS
SMOOTH OUT POWER FLOW
BECAUSE WE CAN’T STORE POWER
WE CAN STORE ELECTRICITY, BUT NOT POWER
FOR A BUILDING WITH 277/480 VOLT, THREE-PHASE, FOUR WIRE SERVICE, TYPICALLY THE ELECTRIC LIGHTING RUNS ON HOW MANY VOLTS?
277 VOLTS
120 V SINGLE PHASE 2 WIRE (LIKE A SHED)
ONE 120 VOLT SINGLE PHASE 2 WIRE IS FOR A SMALL BUILDING
ONE NEUTRAL WIRE
WE HAVE A HOT WIRE AT 120V GOING INTO THE BUILDING AND A NEUTRAL
IF THE CIRCUIT IS ON, ELECTRICITY RUNS THROUGH THE WIRE AND LIGHTS UP THE BULB
120 VOLT / 240 VOLT, SINGLE PHASE, 3 WIRE (LIKE A HOUSE)
ONE 120 V WIRE FOR SOME CIRCUITS IN THE HOUSE
YET ANOTHER 120 V WIRE FOR OTHER CIRCUITS IN THE HOUSE
ONE NEUTRAL WIRE
CERTAIN APPLIANCES REQUIRE MORE WATTAGE IE 240V
WHICH CONNECTS THE TWO 120V LINES
HIGHER VOLTAGE/WATTAGE APPLIANCES
AIR CONDITIONING SYSTEM (WHICH RUNS ON 240)
ELECTRIC RANGE
ELECTRIC DRYER
120 VOLT / 208 VOLT, 3 PHASE, 4 WIRE
ONE 120 V WIRE
ANOTHER 120 V WIRE
AND YET ANOTHER 120 V WIRE
ONE NEUTRAL WIRE
ELECTRONS ARE MOVING BACK AND FORTH BUT THEY ARE NOT IN PHASE, THEY ARE STAGGERED
STAGGER MAKES IT SO THAT THERE IS ALWAYS ELECTRONS MOVING THROUGH ONE OF THE THREE WIRES
SO IN THIS CASE WE HAVE 120 + 120 + 120 = 208 WHICH IS
120 TIMES THE SQUARE ROOT OF 3
208 V FOR THINGS THAT NEED MORE POWER
277 VOLT / 480 VOLT, 3 PHASE, 4 WIRE (FOR LARGE BUILDINGS)
(SIMILAR AS THE LAST SETUP BUT WITH HIGHER VOLTAGE)
ONE 277 V WIRE
ANOTHER 277 V WIRE
AND YET ANOTHER 277 V WIRE
ONE NEUTRAL WIRE
MICRO TRANSFORMERS THAT TAKE 277 V AND STEP THEM DOWN TO 120 AROUND BRANCH CIRCUITS SERVICES ROOMS OUTLETS
POWER AND ELECTRICITY
POWER WE CAN NOT STORE
ELECTRICITY IS POWER OVER TIME
3-WAY SWITCH
FAMILIARIZE YOURSELF W HOW IT WORKS, TOGGLING ON/OFF FROM EITHER SWITCH, IT WILL GO ON/OFF REGARDLESS OF IF IT IS UP OR DOWN
***(SIMILAR TO HOW THE L-SHAPE HALLWAY WORKS AT HOME)***
4-WAY SWITCH
FAMILIARIZE YOURSELF W HOW IT WORKS
DOUBLE-POLE SINGLE-THROW SWITCH
FAMILIARIZE YOURSELF W HOW IT WORKS
ACOUSTICS
HOW LONG WILL IT TAKE BETWEEN WHEN THE SOURCE SOUND IS MADE AND THE RECEIVER SOUND IS HEARD FROM 20 FEET APART?
20 MILLISECONDS SINCE IT IS 1 FOOT PER MILLISECOND
WHEN SOUND IMPINGES ON A SURFACE OF A BUILDING, IE THE INTERIOR
SOME OF THE ENERGY PASSES THROUGH
SOME OF THE SOUND ENERGY IS ABSORBED
AND REASSIGNED AS HEAT IN THE MATERIAL
MOLECULES INSIDE OF THE BUILDING MATERIAL
WHEN THEY ARE IMPINGED UPON BY THE SOUND ENERGY, THEY MOVE, AND AS THEY RUB TOGETHER THEY LOSE SOME OF THE ENERGY THROUGH FRICTION
FINALLY SOME OF THE ENERGY IS REFLECTED
ALL THREE ARE HAPPENING SIMULTANEOUSLY: TRANSMISSION, ABSORPTION, AND REFLECTION
GLASS: A LOT OF SOUND IS TRANSMITTED INTO THE ROOM, NOT MUCH IS ABSORBED, SOME REFLECTED
CONCRETE: SOME SOUND IS TRANSMITTED INTO THE ROOM, A LITTLE BIT IS ABSORBED, SOME REFLECTED
CONCRETE WITH FIBERGLASS FIBER LAYER: LITTLE SOUND TRANSMITTED INTO THE ROOM, A LOT OF IT IS ABSORBED, NOT MUCH REFLECTED
WHEN DO WE USE SOUND ABSORBING MATERIALS?
WHEN WE HAVE EXCESSIVE REVERBERATION ESPECIALLY FOR IE A LECTURE ROOM, ETC
SPECULAR REFLECTION (SOUND BOUNCING)
ANGLE OF REFLECTION = THE ANGLE OF INCIDENCE
REVERBERATION TIME
THE AMOUNT OF TIME IT TAKES FOR A SOUND TO DROP BY 60 DECIBELS
ESTABLISH MAX NOISE LEVELS
A-WEIGHTED DECIBELS (dBA)
NOISE CRITERIA
IBC REQUIRES A MIN LEVEL OF 50 BETWEEN UNITS IN MULTIFAMILY HOUSING
SOUND TRANSMISSION CLASS (SDC)
IMPACT INSULATION CLASS (IIC)
SPACE FOR UNAMPLIFIED MUSIC PERFORMANCE IS TOO DRY (SOUND DIES TOO QUICKLY)
REVERBERATION TIME (RT)
NOISE REDUCTION COEFFICIENT (NRC)
FIELD TEST MEASUREMENTS INCLUDE INFLUENCE OF FLANKING NOISE
TRANSMISSION LOSS (TL)
SOUND TRANSMISSION CLASS (STC)
IMPACT INSULATION CLASS (IIC)
HIGHER NUMBER VALUE ASSOCIATED WITH QUIETER ROOMS
NOISE REDUCTION COEFFICIENT (NRC)
TRANSMISSION LOSS (TL)
SOUND TRANSMISSION CLASS (STC)
IMPACT INSULATION CLASS (IIC)
LIGHTING
***LAMP CAN BE CALLED BULB IN LINGO OF LIGHTING***
DESPITE THE FULL HEIGHT APERTURES ON THREE WALLS OF SCREENED-IN PORCHES, OCCUPANTS JUDGE THE SPACES TO BE DARK, WHAT IS THE EXPLANATION FOR THAT?
THE DARK COLORED FLOOR, CEILING, AND MULLIONS PRODUCES EXCESS CONTRAST
LIGHT IS FOUR DIMENSIONAL
BRIGHTNESS
COLOR
TIME
CONTRAST
IRIS
COLORED PART OF THE EYE THAT CONTROLS THE AMOUNT OF LIGHT THAT ENTERS THE EYE
WILL OPEN OR CLOSE
IT WILL ALLOW MORE LIGHT IN WHEN IT IS A DARK ENVIRONMENT AND LESS LIGHT IN WHEN IT IS A BRIGHT ENVIRONMENT
AN ENVIRONMENT THAT HAS MANY DARK SURFACES
IE FLOORS, WALLS, MULLIANS
AND AROUND THEM THERE ARE BRIGHT SURFACES IE VIEWS TO OUTSIDE
THE DARK SURFACES CONFUSES YOUR EYES
YOUR EYES WILL TREAT IT AS IF IT IS A DARK ENVIRONMENT TO PROTECT YOUR EYES
HOW WE MEASURE LIGHT
HOW MUCH LIGHT IS COMING OFF OF A LAMP
LUMENS
LIGHT LEVELS IN IE HOW MUCH LIGHT COMING OFF OF THE BULB
RECEIVER
WHAT IS FALLING ON THE DESK HEIGHT
LIGHT SHELF
SHADES THE NEAREST SPACE CLOSEST TO THE WINDOW
ISSUE WITH DAYLIGHTING IS BRINGING LIGHT INTO THE DARKEST PART OF THE ROOM
INCANDESCENT LAMP
(INCLUDES TRADITIONAL INCANDESCENT AND HALOGEN)
ADVANGATES
VERY HIGH COLOR RENDITION
ALL COLORS THAT WE CAN SEE ARE IN THE LAMP
CRI OF 100
DISADVANTAGES
GIVES OFF A LOT OF HEAT
90-93% OF WATTS IN IT ARE COMING OUT AS HEAT
A LOT OF WATTS GOING IN AND NOT MUCH LUMENS COMING OUT
WILL NEED TO USE EVEN MORE WATTS FOR AC TO COOL SPACE THAT IS BEING LIT BY HOT SOURCES
DO NOT LAST THAT LONG, BUT ARE VERY INTERCHANGEABLE
FLUORESCENT LAMP
DIFF TECHNOLOGY THAN INCANDESCENTS, INSTEAD OF HEATING UP A FILAMENT IT USES PHOSPHORUS (POWDER)
DISCHARGE LAMP (OLDER TECHNOLOGY)
ADVANTAGES
HIGHER EFFICACY (WE GET MORE LUMENS PER WATT) BUT QUALITY OF LIGHT IS NOT SO GOOD
MUCH COOLER, PRODUCES LESS HEAT
DISADVANTAGES
QUALITY OF LIGHT IS NOT AS GOOD
CRI RANGES BETWEEN 70-85ISH
METAL HALIDE LAMP
ADVANGATES
CRI 85, WHICH IS PRETTY GOOD
PRODUCES A COOL LIGHT (SO IT HAS A HIGH TEMPERATURE)
USED IN STADIUMS, ETC,
DISADVANTAGES
HIGH INTENSITY DISCHARGE LAMP, INSTEAD OF POWDER, IT USES A GAS TO LIGHT UP
TAKES A LONG TIME TO TURN ON
HIGH PRESSURE SODIUM LAMP
ADVANTAGES
EFFICIENT, VERY LONG LIFE
GOOD FOR IE STREET LIGHTS, CAN LAST UP TO 25,000 HOURS
DISADVANTAGES
LOW CRI OF 20, NOT ALL THE COLORS COME OUT (MAINLY YELLOWS, NOT SO MUCH OF BLUES)
USED FOR OUTDOOR APPLICATIONS, COLOR RENDITION IS NOT TOO GOOD, WARM COLOR
YELLOWS COME OUT WELL BUT NOT SO MUCH OF BLUES
LOW PRESSURE SODIUM LAMP
(IT IS NOT USED ANYMORE)
HIGH PRESSURE SODIUM REPLACED LOW PRESSURE SODIUM LIGHT
DISADVANTAGES
IT HAS A CRI OF PRACTICALLY 0 (OR MAYBE 1), ALL COLORS COME OUT GREY
LED LAMP
TOTALLY DIF TECHNOLOGY
ADVANTAGES
VERY HIGH CRI ABOUT 85 OR SO
PRODUCE VERY LITTLE HEAT
CAN LIGHT UP IN ANY COLOR
DISADVANTAGES
FADE OUT IF SCREWED INTO OLD SOCKETS
PERTAINING TO THE LIST OF LIGHT TYPES ABOVE (TOP DOWN) IN GENERAL WE ARE MOVING FROM
SHORTER LAMP LIFE TO LONGER LAMP LIFE
LESS EFFICIENT TO MORE EFFICIENT
BETTER CRI TO WORSE CRI
MORE INTERCHANGEABLE TO LESS INTERCHANGEABLE
MORE HEAT PRODUCED TO LESS HEAT PRODUCED
MORE INSTANT-ON TO TAKES A WHILE TO WARM UP/TURN ON
CORRELATED COLOR TEMPERATURE
COLOR THE LIGHT APPEARS IE BLUEISH (WARMER) VS IE YELLOWISH (COOLER)
***LIGHTS MAY LOOK ‘COOLER’ IF THEY ARE MORE BLUEISH AND ‘WARMER’ IF THEY ARE MORE YELLOWISH BUT THE LOOK OF THE COLOR OF THE LAMP IS OPPOSITE TO THE ACTUAL TEMPERATURE***
THE LOWER THE TEMPERATURE, THE WARMER THE LIGHT (THE COLDER = THE MORE YELLOWISH)
THE HIGHER THE TEMPERATURE THE COOLER THE LIGHT (THE HOTTER = THE MORE BLUEISH)
LUMENS
MEASUREMENT OF LIGHT IN A SOURCE
LUMENS PER WATT MEASURED IN EFFICACY
WE WANT MORE LUMENS PER WATT, THAT MAKES FOR A MORE EFFICIENT LIGHT
BALLAST
PIECE OF EQUIPMENT THAT REGULATES THE CURRENT
STARTING CURRENT > CONTINUATION CURRENT
SOMETIMES THE BALLAST IS INSIDE THE LIGHT FIXTURE
OLD VERSIONS USED TO BE CALLED MAGNETIC (THEY SOMETIMES HUMMED)
NEW VERSIONS CALLED ELECTRIC
BALLAST HAS TO BE COMPATIBLE WITH THE FIXTURE
MIGHT SCREW IN BUT STILL DOES NOT WORK IF BALLAST IS NOT THE RIGHT ONE FOR THAT FIXTURE
DISCHARGE LAMPS REQUIRE BALLASTS
FLUORESCENT
METAL HALIDE
HIGH PRESSURE SODIUM
WAYS WE MEASURE LIGHT/LAMPS
CRI (COLOR RENDERING INDEX)
0-100 (100 MEANS ALL COLORS PRESENT)
CORRELATED COLOR TEMPERATURE
MEASURED IN DEGREES K (COLOR THE LAMP LOOKS LIKE)
HIGHER COLOR TEMP = A BLUER LIGHT
LOWER COLOR TEMP = MORE YELLOWISH LIGHT
EFFICACY (EFFICIENCY OF THE LIGHT
MEASURED IN LUMENS PER WATT
LAMP LIFE
HOW LONG THE LIGHT LASTS (HRS) BEFORE IT NEEDS TO BE REPLACED
LAMP TYPES CRI CCT TEMP IN K EFFICACY LAMP LIFE (HRS)
INCANDESCENT 100 2500 DEGREES 20 2000
FLUORESCENT 80 ??? 70 15000
METAL HALIDE 85 4000 DEGREES 80 15000
HIGH PRESSURE SODIUM 20 2000 DEGREES 100 25000
LED 85 ??? 90+ 85
https://www.youtube.com/watch?v=0Az05_jzgNw
INCANDESCENT
INCANDESCENT AND HALOGEN
DISCHARGE
REQUIRES BALLAST TO START THE CHARGE AND THEN MAINTAIN IT
DISCHARGE AND HIGH INTENSITY DISCHARGE
DISCHARGE: FLUORESCENTS & NEONS
HIGH INTENSITY DISCHARGE: METAL HALIDE AND HIGH PRESSURE SODIUM, THERE ARE ALSO LOW PRESSURE SODIUM AND MERCURY VAPOR LAMPS (REPLACED BY METAL HALIDE, AND LOW PRESSURES ARE REPLACED BY HIGH PRESSURES)
MISC IMPORTANT
FOOTCANDLES
ONE LUMEN PER SQUARE FOOT
BRITISH MEASUREMENT
USING THE METRIC SYSTEM LUMEN IS MEASURED BY A SQUARE METER OR A LUX
THUS A FOOTCANDLE IS = TO APPROX 10 LUX (OR 10.57 LUX TO BE EXACT)
LAMP LUMENS
AVAILABLE LIGHT PER ‘BULB’
LAMPS PER FIXTURE
‘BULBS’ PER LAMP
NUMBER OF FIXTURES
JUST WHAT YOU THINK IT IS/WHAT IT SOUNDS LIKE
CU = COEFFICIENT OF UTILIZATION
% OF LIGHT THAT REACHES THE WORKPLANE (0<CU<1)
(LOSS DUE TO ABSORPTANCE BY FIXTURE AND ROOM SURFACES, GEOMETRY AND COLOR)
LLF = LIGHT LOSS FACTOR
ALSO % OF LIGHT THAT REACHES THE WORKPLANE (0<LLF<1)
(LOSS DUE TO LAMP LUMEN DEPRECIATION, DIRT, BALLAST FACTOR)
IF WE HAVE LLF = 0.9
IT MEANS THAT 10% OF THE LIGHT IS LOST
[LUX]
WHENEVER ‘LUX’ IS IN THE BRACKETS LIKE ABOVE IT MEANS UNITS IN METRIC VERSION
DAYLIGHT FACTOR
MEASURE OF HOW WELL LIT YOUR ROOM IS
TAKE MEASUREMENT INSIDE WITH LIGHT READER
FOR DAYLIGHTING, IT IS BETTER TO HAVE A WINDOW HIGHER THAN LOWER TO ACHIEVE MORE DEPTH IN THE ROOM/SPACE
WATTS
VOLTS x AMPERES x POWER FACTOR
SOUND
LAMBDA (λ) = WAVELENGTH, FT (M)
C = VELOCITY OF SOUND, FPS (M/S)
F = FREQUENCY OF SOUND, HZ
WHAT IS THE WAVELENGTH ASSOCIATED WITH MIDDLE C?
SOUND TRAVELS AT 1130 FT PER SEC
FREQUENCY OF MIDDLE C IS 261 Hz
1130 / 261 = 4.3 FT IS THE WAVELENGTH
HUMAN HEARING RANGE
FROM 20 TO 20,000 Hz
20 Hz = 56 FEET
20,000 Hz = .75 OF AN INCH
NRC = NOISE REDUCTION COEFFICIENT
A = TOTAL SABINS (SOUND ABSORBING UNITS)
S = TOTAL SURFACE AREA IN THE ROOM
VERTICAL TRANSPORTATION
ELEVATORS AND ESCALATORS
ELEVATOR (TYPES)
HYDRAULIC
CHAINED HYDRAULIC (MID-RISE BUILDINGS)
2 RAILS ON EA SIDE OF HYDRAULIC JACK
2 PULLEYS ATTACHED TO TOP OF HYDRAULIC JACK
2 CHAINZ TIE TOGETHER THE SYSTEM
CONTROLLER AND PUMP ARE JUST NEAR THE RAILS
ROPED HYDRAULIC (2-3 FLOOR BUILDINGS)
2 RAILS ON EA SIDE OF HYDRAULIC JACK
1 PULLEY ATTACHED TO TOP OF HYDRAULIC JACK
2 HOISTING ROPES TIE TOGETHER THE SYSTEM
1 AT THE BOTTOM OF THE CAB
1 AT THE BASE OF THE RAILS
CONTROLLER AND PUMP IN A NEARBY MACHINE ROOM
TRACTION (IN MOST BUILDINGS LOW RISE OR HIGH RISE)
OPERATED W A MOTOR, COUNTERWEIGHT, AND ROPE
MOTOR ATTACHED AT THE TOP OF THE RAIL SYSTEM
ROPES ARE ATTACHED TO MOTOR THROUGH AN AXEL
COUNTERWEIGHTS ARE USED TO OFFSET THE WEIGHT OF CAB
ALLOWS TO WORK MORE EFFICIENTLY
(GEARLESS USES LESS POWER WHETHER MR OR MRL)
ESCALATORS
SLOPE: 30 DEGREES TO 35 DEGREES
SPEED: 100 TO 125 FEET PER MIN
CLEARANCE: 7 FT VERT CLEARANCE REQUIRED
CAPACITY: 1.25 PEOPLE PER TREAD
MAX RISE: 20 TO 40 FT, 60 FT IF SUPPORTED
ROOFS
DRAINS
IN LOW SLOPED ROOFS, DRAINS SHOULD BE PLACED MIDSPAN, BETWEEN STRUCTURAL SUPPORTS DUE TO DEFLECTION
THAT IS WHERE PONDING OCCURS
2:12 ROOF AS A PERCENTAGE
VERTICAL DISTANCE / HORIZONTAL UNIT IT 2/12 = 0.17 (17%)
LOW SLOPED ROOF CONSTRUCTION TYPES
SLOPE THE STRUCTURE: SLOPE THE STRUCTURAL MEMBERS THAT SUPPORT THE ROOF DECK
TAMPERING THE STRUCTURE: TAPER THE STRUCTURAL MEMBERS THAT SUPPORT THE ROOF DECK
TAPERING THE INSULATION: BUILD LEVEL DECK THEN OVERLAY WITH TAPERED INSULATION BOARD
HOW TO ACCOUNT FOR AND ADDRESS A BLOCKED ROOF DRAIN IN A LOW SLOPED ROOF?
SECONDARY SYSTEM OF BACKUP DRAINS AND OVERFLOW SCUPPERS. BACK UP DRAINS TO BE 2” HIGHER FOR STANDING WATER, ETC
PENETRATIONS
PITCH PAN HAS MOST POTENTIAL TO LEAK
CONE-SHAPED BOOT LESS LIKELY TO LEAK, MECHANICALLY SENDING THE WATER DOWN FROM THE SIDES VS A FLUID AS MENTIONED ABOVE
CRICKET USES GEOMETRY TO SOLVE FOR LEAKS AND SUCH, IT IS ESSENTIALLY A PITCHED ANGLE TO HELP ROOF FLOW AROUND THE SIDES OF IE A CHIMNEY
WOOD
GETS ATTACKED BY
TERMITES
FUNGUS
OUT OF ALL STRUCTURAL BUILDING MATERIALS
WOOD IS THE MOST LEAST DENSE
LAYERS THAT HAVE LIVING CELLS
CAMBIUM
SAPWOOD
STEEL
WHICH IS STRONGER, COLD ROLLED STEEL OR MILD ROLLED STEEL?
COLD ROLLED STEEL
MOST STRUCTURAL MEMBERS ARE MILD
COLD FORMED, COLD ROLLED, OR COLD DRAWN STEEL
STRONGER STEEL FOR CABLING FOR BRIDGES, ETC
WHICH HAS MORE CARBON, CAST IRON OR ROT IRON?
CAST IRON
CARBON CONTENT IS THE KEY TO STEEL BEHAVIOR
IF TOO MUCH IT IS HARD AND BRITTLE
IF TOO LITTLE IT'S MALLEABLE BUT WEAKER
WE WANT JUST THE RIGHT AMOUNT OF CARBON FOR THE RIGHT MALLEABILITY, AND FOR THE RIGHT STRENGTH
CAST IRON
HAS A LOT OF CARBON SO IT IS STRONG BUT BRITTLE
ROT IRON
HAS LESS CARBON SO IT IS MALLEABLE BUT IT IS WEAKER
GIRDER
IS LARGER THAN A BEAM
ESSENTIALLY A LARGER BEAM THAT SUPPORTS SMALLER BEAMS
COLUMNS AND GIRDERS ARE MAIN STRUCTURES
SUPPORT BEAMS AND THEN EVEN OTHER MORE SECONDARY STRUCTURES
BEAM DEPTH SHOULD BE
1/20 OF BEAM SPAN
IE IF 60’ SPAN, DEPTH SHOULD BE 3’
GIRDER DEPTH SHOULD BE
1/15 OF SPAN
WIDTH OF BEAM OR GIRDER SHOULD BE
1/3 OF DEPTH
OPEN WEB JOIST DEPTH SHOULD BE
1/20 OF SPAN
FOR ROOFS OR LIGHTLY LOADED FLOORS OR CLOSELY SPACED JOISTS
1/24 OF SPAN
DECKING PLUS CONCRETE TOP OF IT ALSO ABOUT
1/24 SPAN
STEEL DECKING DEPTH IS
1/40 OF SPAN
TRIANGULAR STEEL TRUSSES DEPTH SHOULD BE ABOUT
1/4 OF SPAN
RECTANGULAR STEEL TRUSSES DEPTH SHOULD BE ABOUT
1/8 OF SPAN
STEEL COLUMN SIZING
BASED ON TOTAL AREA OF FLOOR THAT THE COLUMN WILL BE HOLDING UP ABOVE IT; ALL FLOORS ABOVE IT
AS COLUMN SPACING GETS WIDER, AND BUILDING GETS TALLER, WE WILL CORRESPONDINGLY NEED A BEEFIER COLUMN
WHAT MAKES SS DIFF FROM STEEL
MORE RESISTANT TO WEATHERING
THIS WAS A QUESTION ON PDD EXAM
WHAT IS THE DIFF BETWEEN I-BEAM AND WIDE FLANGE BEAM?
I BEAM HAS BEEN REPLACED BY WIDE FLANGE, I BEAM HAS A WIDER FLANGE AND IS MORE STRUCTURALLY EFFICIENT
IF THE SPAN IS LARGER THAN WHAT A STANDARD BEAM DEPTH CAN HANDLE WE HAVE SOME OTHER CHOICES/OPTIONS
CASTELLATED BEAMS
ZIG-ZAG CUT OUT AND TOP PORTION IS LIFTED UP, MOVED OVER, PUT BACK DOWN, REWELDED
THIS CREATES A DEEPER, LIGHTER BEAM WITH OPENINGS THAT CAN BE USED FOR PENETRATIONS SUCH AS PIPES, ETC
PLATE GIRDERS
CUSTOM WIDE FLANGE, WIDER OR NARROWER DEPENDING ON THE FORCES APPLIED TO IT
STEEL ARCHES
USE NATURAL GEOMETRY OF A COMPRESSION ARCH
CABLE STAYS
USED IN TENSION TO ACHIEVE LARGER SPANS
STANDARD SHAPES INCLUDE
STANDARD CHANNEL
STRUCTURAL TEE
ANGLES W EQUAL LEGS
ANGLES W UNEQUAL LEGS
WIDE FLANGE PROPORTIONS
W12X45: (TALL AND NARROW) USED FOR BEAMS
W12X120: (SQUARE-ISH) FOR FOUNDATION PILES AND FOR COLUMNS
HOW DEEP IS A W12X120?
12 MEANS IT IS 12’ DEEP
120 MEANS IT IS 120 LBS PER LINEAR FOOT
WHICH OPEN WEB STEEL JOIST TYPE SPANS THE LONGEST?
K IS MOST COMMON AND SPANS UP TO 60’
LH IS LONG SPAN AND SPANS UP TO 96’
DLH IS DEEP LONG SPAN AND SPANS UP TO 150’
CONNECTIONS
TYPICALLY BOLTED OR WELDED OR SOME COMBINATION
SLIP-CRITICAL
BOLTING TECHNIQUE PUTS THE BOLT IN TENSION USING HIGH STRENGTH BOLTS
GALLING
WHEN STEEL ‘TEARS’
WELDS TO BE FAMILIAR WITH
FILLET WELD
DOUBLE FILLET WELD
V-GROOVE WELD
PUDDLE WELD
SINGLE-BEVEL GROOVE WELD W/ BACKUP BAR
DOUBLE-BEVEL GROOVE WELD
PARTIAL-PENETRATION SINGLE-BEVEL GROOVE WELD
V-GROOVE WELD W/ BACKUP BAR
ELEMENTS OF WIDE FLANGE
FLANGES (TOP AND BOTTOM WIDTHS OF THE ‘I’ )
WEB (DEPTH OF THE ‘I’)
CONNECTIONS
A BEAM BETWEEN 2 COLUMNS WITH SHEAR CONNECTION AND THE BEAM BENDS, THE COLUMNS STAND STRAIGHT, THEY DON'T BEND
IF THERE ARE LATERAL FORCES FROM THE SIDES IE WIND, THAT IS A PROBLEM
IF WE HAVE A BEAM BETWEEN 2 COLUMNS WITH A MOMENT CONNECTION AND THE BEAM BENDS, THAT WILL INDUCE SOME BENDING IN THE COLUMNS TOO
STRONGER RESISTANCE TO LATERAL FORCES
STIFFENER PLATES
A PIECE OF PLATE THAT HELPS SHORE UP THE WEB OF THE COLUMN SO IT CAN HANDLE A BEAM
BACKUP BARS
USED AS A SHELF TO MAKE FOR EASE OF ERECTION
BUT MORE SO TO PREVENT THE WELDING ARC FROM BURNING RIGHT THROUGH THE FLANGE
HOW DO YOU ATTACH COLUMNS VERTICALLY IF THEY CAN NOT BE SHIPPED IN FULL LENGTHS OF THE HEIGHT OF YOUR BUILDING?
SPLICE THEM TOGETHER AND WELD THEM WITH THIRD MEMBER PLATES TO MAKE THEM INTO A COMPOSITE SINGLE COLUMN
HOW DO STEEL COLUMNS DISTRIBUTE THEIR LOAD TO THE CONCRETE FOUNDATION?
STEEL BASE PLATES, TYPICALLY ON A BED OF GROUT, BASE PLATES HELD DOWN WITH ANCHOR BOLTS, LEVELING NUTS USED TO MAKE SURE COLUMN IS TRULY VERTICAL
WHAT ARE DOG BONE CUTS FOR?
IF THERE IS AN EARTHQUAKE, THEY MAKE IT SO THINGS BEND BUT DON’T BREAK
SO THERE WILL BE A DEFORMATION AT THE JOINT INSTEAD OF A CATASTROPHIC FAILURE
COPING
REMOVE PART OF THE FLANGE AT INTERSECTIONS AND/OR AREAS OF CONFLICT
BRACED FRAMES
ALLOW STRUCTURAL FRAME TO RESIST LATERAL LOADS
THEY CAN BE APPLIED TO ONLY ONE BAY OF A BUILDING, OR ONE EVERY SEVERAL BAYS DEPENDING ON SIZE
BRACING THE WHOLE BUILDING WOULD BE WAY MORE LABOR INTENSIVE AND COSTLY
WHEN DO WE PREFER AN ECCENTRICALLY BRACED FRAME?
BRACED FRAME |/\| VS ECCENTRICALLY BRACED FRAME |/ \|
ECCENTRICALLY BRACED FRAMES ARE USEFUL FOR EARTHQUAKES AS THEY RESIST LATERAL SEISMIC FORCES WITHOUT BUCKLING
CONCRETE SHEAR WALLS
ALSO HELP WITH LATERAL SUPPORT SIMILAR TO BRACED FRAMES
NEEDED IN THE XY (IE EAST-WEST), XZ (IE NORTH-SOUTH), AND YZ (IE IN THE FLOOR PLATES) DIRECTIONS
TYPICALLY SHEAR WALLS AROUND ELEVATOR CORES, CHASES, ETC
MOMENT FRAMES AND LOADS IN GENERAL
TYPICAL LATERAL LOADS ARE FROM WIND AND EARTHQUAKES BUT THERE ARE ALSO ECCENTRIC LOADS
IE LOADS THAT WANT TO TOPPLE SOMETHING (LIKE A RETAINING WALL) OVER
LOADS WHERE WE ARE TRANSFERRING WEIGHT OF STRUCTURE TO COMPETENT SOILS
TRANSFER LOADS, IF WE REMOVE A COLUMN, THE WEIGHT OF COLUMN ABOVE WOULD NEED TO BE TRANSFERRED OVER, COLUMN THAT IT RESTS ON WOULD NEED TO BE THICKER/DEEPER
FULLY RESTRAINED (FR) MOMENT CONNECTIONS: HAVE SUFFICIENT STRENGTH TO TRANSFER MOMENTS WITH NEGLIGIBLE ROTATION BETWEEN CONNECTED MEMBERS
PARTIALLY RESTRAINED (PR) CONNECTION: HAVE SUFFICIENT STRENGTH TO TRANSFER MOMENTS WITH ROTATION BETWEEN CONNECTED MEMBERS
RECAP ON FOUR TYPES
MOMENT-RESISTING FRAME
SHEAR WALL
BRACED FRAME
ECCENTRICALLY-BRACED FRAME
STAGGERED TRUSS SYSTEM
EVERY OTHER FLOOR IS A TRUSS AND IT SPANS THE FULL WIDTH OF BUILDING AND FULL HEIGHT OF FLOOR
EACH TRUSS IS GOING TO HOLD THE FLOOR ABOVE IT AND BELOW IT
ALLOWS FOR THE FLOOR STRUCTURE DEPTH TO ONLY BE THE THICKNESS OF THE SLAB
RIGID CORE VS RIGID PERIMETER
RIGID PERIMETER OFFERS MORE LATERAL SUPPORT BECAUSE IT ACTS OVER A LARGER AREA
WHY WOULD WE CURVE A BEAM?
CAMBER
TO PRE CURVE SOMETHING IN AN UPWARD DIRECTION TO BETTER RESIST LOADS AND BE MORE FLAT WHEN FULLY LOADED
COMPOSITE STEEL AND CONCRETE WORKS WELL FOR COLUMNS BUT WHY DON’T WE USE FOR BEAMS?
BEAMS WOULD BE TOO HEAVY
WHAT IS A SHEAR STUD, IS IT A WALL ELEMENT OR A FLOOR ELEMENT?
IT IS A FLOOR ELEMEN
ATTACHES A CONCRETE DECK TO A STEEL BEAM (PICTURE AT A CROSS SECTION IN THE FLOOR)
GIRTS
METAL CHANNELS, IE Z CHANNELS, THAT SPAN ACROSS STEEL COLUMNS, THEY RECEIVE THE EXTERIOR PANELING AND HOLD IT IN PLACE
COME IN VARIOUS SHAPE
Z-BAR
C-CONNECTION
U-BAR
L-BAR
UPSTAND C
UPSTAND B
NOTCHED Z-BAR
HAT BAR
CONCRETE CURB
WHAT'S A TAGLINE?
ROPES ATTACHED TO STEEL THAT IS BEING CRANED IN PLACE FOR SOMEONE ONSITE TO LOCATE THEM SPECIFICALLY WHERE THEY NEED TO BE RECEIVED
WHAT ARE DRIFT-PINS?
ONCE A TAGLINE IS HANGING THE BEAM IN PLACE, DRIFT PINS (TAPERED STEEL PINS) ARE PLACED THROUGH THE BOLT HOLES TEMPORARILY TO HOLD THE BEAM IN PLACE UNTIL THE ACTUALLY BOLTS ARE PUT IN FOR A PERMANENT CONNECTION
HOW MANY STORIES CAN A STEEL BUILDING BE IF A STRUCTURE IS UNPROTECTED FROM A FIRE?
5 STORIES
STEEL DOES NOT REALLY BURN, IT SOFTENS, 5 STORIES GIVES OCCUPANTS ENOUGH TIME TO FLEE THE BUILDING
ONCE FIREPROOF (AKA FIRE RESISTING) THERE IS NO LIMIT TO HEIGHT PER CODE
OPTIONS FOR FIREPROOFING
PLASTER ON LATH
WATER + ANTIFREEZE (EXOTIC/RARE OPTION)
REINFORCED CONCRETE
SPRAY-APPLIED RESISTANT MATERIAL (SFRM)
SHEET METAL W LOOSE INSULATING FILL
GYPSUM BOARD
INTUMESCENT PAINT
INTUMESCENT PAINT
APPLIED TO STEEL, IN THE EVENT OF A FIRE, IT EXPANDS AND PROTECTS THE STEEL
ALLOWS US TO EXPOSE THE STEEL WHEN WE NORMALLY WOULD NOT BE ABLE TO
WHEN DON’T WE NEED TO FIREPROOF STEEL STRUCTURAL MEMBERS?
IF WE HAVE A MEMBER THAT HAS A JOB FOR RESISTING LATERAL FORCES ONLY IE CROSS BRACING
WE NEED FIREPROOFING FOR STRUCTURES THAT RESIST GRAVITY LOADS
WHAT IS THE LEAST EXPENSIVE TYPE OF FABRIC USED AS ENCLOSURE?
POLYESTER COATED WITH PVC
BUT IS LEAST DURABLE
DOES NOT KEEP ITSELF TOO CLEAN TOO WELL
GLASS FIBER COATED WITH PTFE (TEFLON)
MORE DURABLE
KEEPS ITSELF THE MOST CLEAN
GLASS FIBER COATED WITH SILICONE
MOST DURABLE
DOESN’T KEEP ITSELF TOO CLEAN EITHER THOUGH
WHAT HAPPENS IN A TENSILE STRUCTURE IF CURVATURE IS TOO SHALLOW OR TENSION MEMBER IS NOT TIGHT ENOUGH?
THE WHOLE STRUCTURE WILL FLUTTER OR DEFLECT UNDER WIND AND RAIN AND SNOW AND GRAVITY LOADS
PNEUMATIC STRUCTURES
INSTEAD OF TENSION HOLDING THE WHOLE THING DOWN, AIR IS BEING PUMPED INTO THE SPACE
VERY ENERGY CONSUMING
HMS ALARM
IRON NAILS HAD TURNED TO MUSH EXCEPT FOR THE ONES WITH PAPER BECAUSE SOMEONE HAD NOT REMOVED THE PAPER FROM AROUND THE NAIL THAT IT WAS SHIPPED IN
FROM THEN ON IT WAS DECIDED THAT IRON NAILS SHOULD NOT COME INTO CONTACT WITH COPPER SKIN IN THE PRESENCE OF SEA WATER
WHAT IS WRONG WITH AN ALUMINUM NAIL THROUGH COPPER FLASHING ON A ROOF DETAIL?
IF WE HAVE TWO METALS TOUCHING WHERE THERE IS GOING TO BE SOME WATER, THERE CAN BE GALVANIC ACTION (AKA GALVANIC CORROSION)
WHEN WE HAVE METALS WITH DIFFERENT GALVANIC NUMBER RANGING FROM ANODE TO CATHODE
SURFACE ANODE (MOST ACTIVE)
ALUMINUM
ZINC
STEEL
IRON
STAINLESS STEEL - ACTIVE
TIN
LEAD
COPPER
STAINLESS STEEL - PASSIVE
FASTENER CATHODE (LEAST ACTIVE)
IF THE SURFACE IE ALUMINUM OR COPPER ROOF IS CLOSER TO THE ANODE SIDE OF THE LIST AND THE FASTENER IS CLOSER TO THE CATHODE SIDE OF THE LIST
IT WILL PROB BE OK
IF THE SURFACE AND FASTENER ARE CLOSE TOGETHER ON THE LIST ARE CLOSE TOGETHER IN NUMBER
IT WILL PROB BE OK
IF THE SURFACE AND FASTENER ARE FAR APART ON THE LIST AND THE SURFACE IS ON THE CATHODE SIDE AND THE FASTENER IS ON THE ANODE SIDE,
THAT IS WHEN YOU HAVE TROUBLE ( ESPECIALLY IN THE PRESENCE OF WATER)
COMMON DIFFICULT ADJACENCIES
COPPER AND GALVANIZED STEEL FASTENERS
UNDER HUMID CONDITIONS OR ROOFS
BRASS AND STEEL GALVANIZED STEEL FASTENERS
UNDER HUMID CONDITIONS OR ROOFS
ALUMINUM AND GALVANIZED STEEL FASTENERS
UNDER HUMID CONDITIONS OR ROOFS
COPPER AND ZINC
STEEL AND ZINC
MORTAR AND ZINC
EVEN CERTAIN WOODS WITH LOW PH LIKE WHITE CEDAR OR DOUGLAS FIR WITH ZINC
EMBODIED ENERGY (GENERAL RULES FOR MATERIALS THAT HAVE HIGHER EMBODIED ENERGY)
MATERIALS THAT ARE MORE FINISHED
HEAVIER
MORE PETROLEUM USED
HIGHER GLUE AMOUNTS
LARGE AMOUNTS OF HEAT IN PRODUCTION
LARGE AMOUNTS OF MINING / REFINING
PERCENTAGE OF MATERIALS THAT ARE RECYCLED
90% OF STEEL IS RECYCLED
30% OF ALUMINUM IS RECYCLED
THERMAL BRIDGING OF METAL STUD VS WOODEN STUD
METAL STUD IS MORE LIKELY TO BE A THERMAL BRIDGE
CONCRETE
USE
BESIDES WATER, MOST WIDELY USED MATERIAL
ROMANS INVENTED IT, FOR 1300 YEARS WE DID NOT KNOW HOW TO MAKE CONCRETE, BUT IN 1820’S IN ENGLAND IT WAS PATENTED AS PORTLAND CEMENT
CONCRETE AND STEEL USUALLY GO TOGETHER
STEEL IS HIDDEN AND IS DOING MOST OF THE WORK
DIFFERENCE BETWEEN CONCRETE VS CEMENT?
CEMENT IS ONE OF THE INGREDIENTS OF CONCRETE ALONG W WATER, AGGREGATE, ETC
CONCRETE DRYING TIME
AT SOME POINT WE HAVE TO DECLARE IT CURED
28 DAYS
CHEMICAL PROCESS
HYDRATION
SHRINKAGE
CAUSES CRACKS
WHICH TYPE OF PORTLAND CEMENT IS MOST COMMONLY USED?
TYPE I (AKA NORMAL CONCRETE)
STRONGEST
TYPE IA (NORMAL CONCRETE THAT IS AIR ENTRAINED WHICH ALLOWS FOR FREEZE AND THAW) (BUBBLES ARE ABOUT 5% OF CONCRETE)
FOR COLD CLIMATE OR MIXED CLIMATES
STRENGTH APPROACHES THAT OF TYPE I
TYPE II
MODERATE RESISTANCE TO SULFATES THAT ARE FOUND IN GROUNDWATER WHICH WEAKEN CONCRETE, CAUSE CRACKS, ETC
TYPE IIA
MODERATE RESISTANCE TO SULFATES AND AIR ENTRAINED
TYPE III
HIGH EARLY STRENGTH CONCRETE
COLD WEATHER
TYPE IIIA
HIGH EARLY STRENGTH CONCRETE AND AIR ENTRAINED
TYPE IV
LOW HEAT OF HYDRATION
UNCOMMON
USED FOR DAMS, ETC
TYPE V
HIGH RESISTANCE TO SULFATES
CONCRETE MIX AGGREGATE SIZE
AGGREGATE GEOMETRIES OF DIFFERENT SIZES SO THAT SMALLER AGGREGATES CAN TUCK BETWEEN THE LARGER ONES
AGGREGATE RULE OF THUMBS
< 3/4 THE SIZE OF SPACE BETWEEN REBARS
< 1/6 DEPTH OF SLAB
LIGHTWEIGHT AGGREGATE
STRUCTURAL: WHICH IS 25% LESS WEIGHT W ABOUT THE SAME STRENGTH THAT USES CRUSHED SHALE THAT IS HEATED AND THEN EXPANDS
NON-STRUCTURE, INSULATIVE AND 80% LESS WEIGHT, USED FOR ROOFS
CONCRETE STRENGTH
LARGE RANGE FROM 2,000 PSI TO ABOUT 20,000 PSI (ALL COMPRESSIVE STRENGTH)
NORMAL CONCRETE APPROX BETWEEN 3,000 TO 4,000 PSI
PRIMARILY DEPENDENT ON WATER IN THE MIX
DRY = STRONG
WET = MORE WORKABLE
ULTRA STRENGTH CONCRETE HAS A SPECIALTY MIX AND A 30,000 PSI
HOW IS CONCRETE MEASURED?
VOLUME IN CUBIC YARDS
~$100/CY
~$75 DELIVERY FEE
~90 MIN TO GET TO JOB SITE BEFORE IT CURES
HOW DO WE KNOW IF CONCRETE IS STRONG ENOUGH?
CONCRETE SLUMP TEST TO DETERMINE HOW WET IT IS
PUT IN METAL CONE
REMOVE CONE
MEASURE HOW MUCH IT SLUMPS
ALSO, WE CAN SEND TO BE TESTED IN A LAB
WHAT IS SELF CONSOLIDATING CONCRETE?
HIGHER PROPORTION OF SMALLER AGGREGATE IN THE CONCRETE WITH ADMIXTURES THAT MAKE IT MORE FLOWABLE, ALLOWS FOR CRISPER EDGES, REQUIRES BEEFIER RESISTANCE IN THE FORMWORK TO MAKE SURE IT DOESN'T BLOW OUT
IS CONCRETE CONSIDERED A GREEN MATERIAL?
NO, NOT PARTICULARLY GREEN
HAS A LARGE CARBON FOOTPRINT
CEMENT MAKING PROCESS REQUIRES HEATING UP MATERIALS AT HIGH TEMPERATURES
TRANSPORTATION OF SUCH HEAVY MATERIAL = MORE CARBON
FLY-ASH CONCRETE CAN BE A BIT MORE OF A ‘GREEN’ OPTION THAN REGULAR CONCRETE
HOW DO WE GET FORMWORK OFF?
NEED TO THINK OF IT GEOMETRICALLY TO HAVE IT BE ABLE TO BE REMOVED
THEN USE FORM RELEASE COMPOUND WHICH WILL BE COATED ON THE FORMWORK IE WAX OR PLASTIC
FORMWORK MIGHT BE MORE EXPENSIVE THAN ALL OTHER CONCRETE COMBINED
REUSABLE FORMWORK MAKES IT MORE ECONOMICAL ESPECIALLY IF IT IS WITH SIMPLER GEOMETRIES
CONCRETE STRENGTH COMPRESSION VS TENSION
STRONGER IN COMPRESSION
NO STRENGTH IN TENSION, THAT IS WHY WE REINFORCE IT WITH STEEL
BOTH CONCRETE AND STEEL HAVE SIMILAR RATES OF EXPANSION
WHEN IT GETS COLD BOTH STEEL AND CONCRETE SHRINK AND WHEN WARM THEY EXPAND AT ALMOST IDENTICAL RATES
WHERE DO WE PLACE REBAR IN CONCRETE?
GEOMETRICALLY WHERE THE LARGEST TENSION FORCES ARE
IE IF WE HAVE A BEAM THAT WE LOAD AND IT WANTS TO DEFORM, WE PLACE IT AT THE MOMENTS OF BENDING
IS REBAR HOT ROLLED OR COLD ROLLED STEEL?
HOT ROLLED (AS FOUND IN STEEL STRUCTURES)
COLD ROLLED IS FOUND IN PRESTRESSED CABLES
WHAT IS THE DIAMETER OF #8 REINFORCING BAR?
1” (AS IT IS MEASURED IN 1/8THS OF AN INCH, 8/8 = 1)
WHAT DOES GRADE 60 REBAR MEAN?
REBAR HAS 60,000 PSI TENSILE STRENGTH WHICH IS MOST COMMON
LOWER GRADE OF 40, AND HIGHER GRADE OF 75 ALSO AVAILABLE
UNDER WHAT CONDITION WOULD WE WANT TO USE 75?
IN COLUMNS BECAUSE WE NEED EXTRA STRENGTH
WHAT MUST BE DONE TO USE STEEL REBAR IN SALTY AREAS IE MARINE ENVIRONMENTS?
COAT THE REBAR WITH EPOXY
GALVANIZED REBAR
STAINLESS STEEL REBAR
ZINC COATED REBAR
POLYMER COATED REBAR
WHAT IS THE MIN SPACING AVAILABLE FOR WELDED WIRE REINFORCING?
WELDED WIRE OF MESH, SPACING RANGES FROM 2” MIN TO 12” MAX
HOW DO WE SPLICE TOGETHER REINFORCING BAR IF/WHEN WE NEED TO IF IT IS NOT LONG ENOUGH?
TYPICALLY OVERLAP THE REBAR BY 30 REBAR DIAMETERS, IF IT IS 1” THEN 30” OF OVERLAP
IN A SITUATION LIKE COLUMNS WHERE WE DO NOT HAVE ENOUGH ROOM BECAUSE IF WE DOUBLE THE THICKNESS OF THE REBAR WE WON'T HAVE ENOUGH ROOM FOR THE CONCRETE TO GO THROUGH THE POUR, WE USE PROPRIETARY CUSTOM REBAR COMBINERS, REINFORCING BAR COUPLERS
CONCRETE BEAMS
STIRRUPS RESIST MODEST DIAGONAL FORCES
BOTTOM BARS HANDLE THE SIGNIFICANT TENSION FORCES THAT HAPPEN WHEN BENDING
U-SHAPED BARS CALLED STIRRUPS RESIST THE DIAGONAL FORCES AT THE EDGES OF THE BEAM
OFTEN SLABS DO NOT REQUIRE STIRRUPS BECAUSE IT IS THE WIDTH OF THE SLAB, SO WE DO NOT NEED THE STIRRUPS
CHAIRS
SUPPORTS THAT KEEP REBAR AT THE APPROPRIATE HEIGHT
IF IT IS A ROW OF THEM AND THEY ARE TIED TOGETHER THEY ARE CALLED BOLSTERS
LEFT IN THE CONCRETE AFTER THE CONCRETE IS POURED
SHRINKAGE TEMPERATURE STEEL
WHAT SLAB NEEDS INSTEAD OF STIRRUPS
STEEL WIRE REINFORCING THAT GOES PERPENDICULAR TO SLAB
***YOU CAN TELL IF YOU ARE LOOKING AT A BEAM OR A SLAB IF YOU NOTICE STIRRUPS VS SHRINKAGE TEMPERATURE STEEL***
COLUMN W VERTICAL BARS AND HORIZONTAL TIES, WHAT IS THE JOB OF EACH?
VERTICAL BARS TAKE UP SOME OF THE VERTICAL COMPRESSION LOADS AND PICK UP SOME TENSILE LOADS FROM WIND LOAD OR EARTHQUAKE, ETC
TIES ARE TO PREVENT OUTWARD BUCKLING
WHAT DOES FIBROUS REINFORCING DO FOR CONCRETE?
MICROFIBER VS MICROFIBER REINFORCING
BAG THROWN INTO THE MIXING PROCESS
CURING PROCESS FIBERS ACT AS TENSION MEMBERS
MICRO HELPS WITH SHRINKAGE AND MAKES IT LESS LIKELY TO CRACK
MACRO FIBER REINFORCING MAY POTENTIALLY REDUCE THE NEED FOR SHRINKAGE TEMPERATURE STEEL
WHAT IS CONCRETE CREEP?
ON ITS OWN WEIGHT WILL SQUISH DOWN, WE NEED TO ALLOW FOR THOSE TOLERANCES
WHAT IS PRESTRESSING?
INTENDED TO WORK IN BENDING, CONCRETE W PRE-TENSIONING CABLE THAT SQUEEZES CONCRETE TOGETHER TO INCREASE THE STRENGTH
WHAT ARE THE DIFFERENCES IN THE FOLLOWING?
PRESTRESSED: SQUEEZING TOGETHER BY TWO OF THE FOLLOWING TYPES
PRE-TENSIONED: PRECAST CONCRETE, CAST IN FACTORY AND TRUCKED ON TO THE SITE
POST-TENSIONED: TUBES THAT ARE RUN THROUGH THE CONCRETE, STRETCHED ACROSS THE FORMWORK, AND PULLED USING A HYDRAULIC JACK TO PULL THE CABLE THROUGH THE TUBES SO IT GOES FROM BEING DROPPED TO BEING PULLED TAUGHT
STEPS FOR CREATING A SLAB ON GRADE CONCRETE PAD (TYP ABOUT 3” - 8” THICKNESS)
SCRAPE TOPSOIL OFF TO REVEAL MORE STABLE SUBSOIL, AND IF NONE AVAILABLE WE ARE GOING TO TRUCK IN SOME FILL THAT IS APPROPRIATELY STABLE
PUT SOME CRUSHED STONE DOWN, APPROX 4” AT LEAST, APPROX 1.5” DIAMETER STONE TO CREATE A CAPILLARY BREAK
PLACE PLASTIC SHEET IE POLYETHYLENE FOR MOISTURE BARRIER
SET UP FORMWORK SUPPORTED BY IN-GROUND STAKES
WELDED WIRE REINFORCING USING CHAIRS ON TOP OF THE PLASTIC (BUT NOT DIRECTLY ON TOP OF THE PLASTIC)
MAKE SURE IT GOES NEAR THE EDGE BUT NOT DIRECTLY TO THE EDGE BECAUSE IT WILL RUST
FOR HEAVIER LOADS, WE WILL USE A GRID OF REBAR INSTEAD OF THE WIRE MESH FABRIC
THEN POUR THE SLAB
THEN SCREED THE SLAB USING THE EDGE OF WOOD OR METAL TO ACHIEVE A LEVEL SURFACE
THEN GIVE SLAB ITS INITIAL FLOATING USING A BULL FLOAT OR A DARBY TO FURTHER FLATTEN, REPEATED AS NECESSARY
EVENTUALLY TROWEL THE SURFACE FOR A SMOOTHER SURFACE STILL
WE WANT TO KEEP THE SLAB DAMP FOR AT LEAST A WEEK, SO IT WILL BE COVERED
LIMIT/CONTROL CRACKING BY USING CONTROL JOINTS EXTEND 1/4 OF THE DEPTH OF THE SLAB
SPACED AROUND 15’ OR SO
THINNER SLABS REQUIRE CLOSER SPACINGS
ISOLATION JOINT CAN SEPARATE DIFFERENT POURS OF CONCRETE BUT CAN VISUALLY LOOK LIKE THE SAW CUTS/CONTROL JOINT
ELIMINATE OR MINIMIZE THE NUMBER OF CONTROL JOINTS BY
USE STRONGER CONCRETE VIA DRIER MIXTURE
USING FLY ASH CONCRETE OFFERS LESS SHRINKAGE
USE ADD MIXTURES THAT ALLOW FOR LESS SHRINKAGE
POST TENSIONING THE WHOLE THING, IF WHOLE THING IS SQUEEZED TOGETHER
USE MICROFIBERS
CONTROL JOINT
EXTEND PARTWAY DOWN THE DEPTH OF THE SLAB AND ARE INTENDED TO LIMIT CRACKING
ISOLATION JOINT
GO ALL THE WAY CLEAR THROUGH THE SLAB, THEY ARE USED FOR EXPANSION/CONTRACTION, SEISMIC, VIBRATION/NOISE ISOLATION, OR BREAKING UP THE IRREGULAR SHAPES OF A BUILDING
USED FOR DEALING W EXPANSION AND CONTRACTION, SEISMIC REASONS, NOISE ISOLATION, AND BREAK IRREGULAR SHAPES UP OF BUILDING AT LEAST FROM A STRUCTURAL POINT OF VIEW
HOW DO YOU CREATE A NON SLIP CONCRETE FINISH?
WITH A STIFF BRISTLE BROOM, DRAGGING IT PERPENDICULAR TO THE DIRECTION OF TRAVEL
WE CAN DO IT WHEN WE TROWEL THE CONCRETE
EITHER TROWEL LESS, SO IT IS ROUGHER, OR DO IT IN A CIRCULAR MOTION
SPRINKLE IT WITH ANTI-SKID POWDER
SAW IN GROVES
KEY
WHERE CONCRETE WALL SITS INSIDE CONCRETE FOOTER
DOWELS
STICK UP OVER FROM THE FOOTER INTO THE AIR AND WHEN THE WALL IS POURED ON TOP OF THE FOOTER THEY STRUCTURALLY TIE THE WALL TO THE FOUNDATION
TIES
SMALL DIAMETER RODS THAT RESIST THE HYDROSTATIC PRESSURE THAT WANTS TO BLOW OUT THE FORMWORK USING WALERS ON THE EXTERIOR/EXPOSED SIDE OF THE BOARD FORM
INSULATING CONCRETE FORMS (ICF’S)
MADE OF POLYSTYRENE, OFFER INSULATION AND REMAIN AS PART OF THE CONCRETE
WHAT IS THE DIFFERENCE IN THE PROCESS OF POURING A WALL VS A COLUMN?
NOT MUCH
COLUMN WILL HAVE A PILE CAP
WALL WILL HAVE A FOOTING
WHY ARE CONCRETE BUILDING CORNERS BEVELED?
CHAMFER LEDGES TO ANGLE THE EDGES SO THAT THEY ARE NOT CRISP
CRISP EDGES ARE NOT PREFERRED BECAUSE WE WANT TO PROTECT CONCRETE FROM WEATHER, PROTECT IT FROM SHOPPING CARTS, ETC HITTING IT, AND PROTECT US FROM SHARP EDGES AD PEOPLE MAY GET HURT BY SHARP EDGES AS SUCH
ALSO PREVENTS THE UGLY FROM HAPPENING WHEN EDGES CHIP OFF AND THE REST OF THE BUILDING STAYS IN GOOD CONDITION
SHARP CORNERS EVEN WHEN DESIRED ARE USUALLY MORE FOR INTERIORS
HOW DEEP SHOULD CONCRETE BEAMS BE?
RATIO OF 1:3 ( 1 WIDE X 3 DEEP)
ONE WAY SLAB
CONSISTS OF COLUMNS, GIRDERS, AND BEAMS WITH A SLAB ON TOP WHERE THE WHOLE THING IS CAST AS A SINGLE CONTINUOUS POUR
ONE WAY SOLID SLAB
GIRDERS ARE GOING TO BE STOUTER AND WIDER
OFFER SHORTER SLAB BAND BETWEEN BEAMS
REDUCE STORY TO STORY HEIGHTS
ONE WAY JOIST SYSTEM (AKA RIBBED SLAB)
CONSISTS OF PRIMARY STRUCTURE OF COLUMNS AND BEAMS WITH JOIST BANDS IN BETWEEN THE BEAMS
THEY ARE BROADENED WHERE THEY MEET THE BEAM TO BEAR INTO THE BEAM
AT MID SPAN, YOU MIGHT NEED A DISTRIBUTION RIB
WIDE MODULE SLAB
IF IE FIRE CODE REQUIRES A THICKER SLAB OF SOMETHING MORE THAN 4”
DUE TO THICKER SLAB, WE CAN USE HALF AS MANY JOISTS
TWO WAY SOLID SLAB
BEST FOR BAYS THAT ARE CLOSE TO SQUARE PROPORTIONS
FOR MAX EFFICIENCY, WE CANTILEVER SLABS 30% OF BETWEEN COLUMN SPANS TO REDUCE BENDING FORCES IN THE MIDDLE AND MAEVEN ELIMINATE THE NEED FOR AN EXTRA BAY OF COLUMNS
TWO WAY FLAT SLAB
BEST FOR FACTORIES, ETC
DROP PANELS TO RESIST SHEAR FORCES NEAR THE TOP OF EACH COLUMN
THICKENED CONCRETE SLAB (SOMETIMES HAVE ADDED MUSHROOM CAPS, MAKE THEM MORE EXPENSIVE)
TWO WAY FLAT PLATE
FOR LIGHTLY LOADED FLOORS
NO DROP PANELS
BETTER FLOOR TO FLOOR HEIGHT
NEEDS EXTRA REBAR WHERE THE COLUMNS ENGAGE
TWO WAY JOIST SYSTEM (AKA WAFFLE SLAB)
SERIES OF PANS PUT DOWN (DOMES) THAT MAKE THE ARRAY OF THE WAFFLE
ABSENCE OF FORMS AROUND THE COLUMNS CREATE ‘HEADS’ (SOMEWHAT LIKE THE DROP PANELS AND SORT OF LOOK LIKE MUSHROOM CAPS)
ONE WAY SLABS
MORE FOR RECTANGULAR BAYS
TWO WAY SLABS
MORE FOR SQUARE BAYS
LIFT SLAB SYSTEM
CASTED FLOOR AND ROOF SLABS IN A STACK AT THE GROUND
MAKE COLUMNS AND POUR FLOORS ONE BY ONE
LIFTED UP WITH HYDRAULIC JACKS TO THE RIGHT PLACE
WELD THEM IN PLACE USING STEEL THAT WAS SET INTO THE CONCRETE
FLYING FORMWORK
LARGE REUSABLE SECTIONS OF FORMWORK TYPICALLY SUPPORTED ON METAL TRUSSES
LIFTED INTO PLACE USING A CRANE
POURING SLAB FLOOR BY FLOOR
SLIP FORMING
SIMILAR CONCEPT AS FLY FORMING BUT FOR WALLS
FORMWORK THAT CREEPS UP, LEAVING FORMED WALL BELOW IT AS IT LIFTS UP
LIFTING RINGS
USED FOR TILT UP CONSTRUCTION
WALLS POURED ON THE GROUND AND TILTED UP WITH A CRANE
THERE MUST BE ENOUGH REBAR TO DEAL WITH THE UNUSUAL FORCES THAT WILL COME FROM LIFTING ITSELF
NOT ONLY TO SUPPORT THE LOADS WHILE THE WALL IS IN PLACE BUT ALSO THE ACT OF TILTING IT UP
SLAB DEPTHS
DEPENDS ON THE TYPE, SEE BELOW:
ONE WAY SOLID SLAB
TYPICALLY 4” TO 10” DEEP
DEPTH OF THE SLAB SHALL BE 1/22 THE SPAN
IF IT IS POST TENSIONED, WE CAN GET AWAY WITH 1/40 THE SPAN
WIDE MODULE SYSTEM
TYPICALLY 3” TO 4.5”
DEPTH OF THE SLAB SHALL BE 1/18 THE SPAN
IF IT IS POST TENSIONED, WE CAN GET AWAY WITH 1/36 THE SPAN
TWO WAY FLAT PLATE SYSTEM
TYPICALLY 5” TO 12” (THICKER BECAUSE NO BEAMS, JOISTS, GIRDERS BELOW IT)
DEPTH OF THE SLAB SHALL BE 1/30 THE SPAN
IF IT IS POST TENSIONED, WE CAN GET AWAY WITH 1/45 THE SPAN
TWO WAY FLAT SLAB SYSTEM
DROP PANEL WIDTH: 1/3 THE SPAN BETWEEN EACH OF THEM
DROP PANEL DEPTH: 1/2 THE DEPTH OF THE SLAB ABOVE IT
WAFFLE SLABS
TYPICALLY 3” TO 4.5” (PLUS THE DEPTH OF THE DOMES)
TOTAL DEPTH OF THE SLAB SHALL BE 1/24 THE SPAN
IF IT IS POST TENSIONED, WE CAN GET AWAY WITH 1/35 THE SPAN
CONCRETE BEAMS
TYPICALLY 1/16 OF SPAN
IF IT IS POST TENSIONED, WE CAN GET AWAY WITH 1/24 THE SPAN
CONCRETE GIRDERS
TYPICALLY 1/12 OF SPAN
IF IT IS POST TENSIONED, WE CAN GET AWAY WITH 1/20 THE SPAN
SPAN OF CONCRETE
CAN BE INCREASED IF WE TAPPER IT, USE VAULTS, ETC
SHOTCRETE
SPRAYED VERTICAL WALLS, ETC
ARCHITECTURAL CONCRETE
EXPOSED CONCRETE THAT WE SEE, EFFORTS ARE PUT IN TO MAKE SURE IT LOOKS GOOD, IE BOARD FORMED CONCRETE
HOW DO WE CUT CONCRETE ONCE IT IS SET?
DIAMONDS IE CIRCULAR BLADES, ELABORATE WIRE CUTTERS
HOW DO CONCRETE STRUCTURES PERFORM IN FIRE?
THEY DO WELL, BUT WE MUST NOT HAVE EXPOSED REBAR
HOW DO CONCRETE STRUCTURES DO IN EARTHQUAKES?
THEY ARE STIFF SO THE COLUMN TIES ARE WHAT WE NEED TO PAY ATTENTION TO, WHERE COLUMNS AND BEAMS MEET
PRECAST CONCRETE
TYPE III PORTLAND CEMENT IS USED
MAX SIZE LIMITS BASED PRIMARILY ON TRANSPORTATION LIMITATIONS
TRUCK BED ~12-14 FEET WIDE x 59 FEET LONG
HOW ARE THE HOLES IN HOLLOW CORE CONCRETE FORMED?
THREE WAYS
STIFF DRY CONCRETE MIX THROUGH EXTRUDER
SLIP FORMED, TUBES MOVE ALONG WITH HOPPER THAN MOVED OUT
BOTTOM PORTION POURED WET, THEN COLLAPSIBLE TUBES PLACED ON TOP AND CONTINUED TO BE POURED ON TOP OVER THEM
DOUBLE T
PRESTRESSING CABLES WITHIN, COMES IN 8’ OR 10’ OPTIONS
OFTEN SEEN IN EXPOSED CEILINGS OF CONCRETE PARKING GARAGES
STIRRUPS
EXTEND ABOVE PRECAST CONCRETE BEAM TO TIE INTO THE SLAB ABOVE IT
FACETENING
TO CONCRETE WITH STEEL THAT IS CASTED INTO IT, NAIL INTO IT WITH SPECIALTY NAILS, DRILL OVERSIZED HOLE AND FILL WITH GROUT AFTER INSERTING BOLT, ETC
JOINTS
PRECAST PANELS USING STEEL THAT IS WELDED OR BOLTED TOGETHER
FOUNDATIONS
STEEL AND GROUT USED TO ATTACH PRECAST MEMBERS, SAME AS PREVIOUSLY DISCUSSED
MASONRY
CEMENT USED IN MORTAR
TYPE I: NORMAL CEMENT
TYPE II: MODERATE SULFATE RESISTANCE
TYPE III: HIGH EARLY STRENGTH
FROM A STRUCTURAL AND MOISTURE POINT OF VIEW, MORTAR IS MORE IMPORTANT THAN THE BRICK ITSELF
MORTARS THAT OFFER HIGHER STRENGTH AND LOWER WATER PERMEABILITY
THOSE MADE WITH PORTLAND CEMENT
MASONRY CEMENTS VS PORTLAND CEMENT
TWO TYPES OF PORTLAND CEMENT USED FOR MASONRY
CEMENT LIME MORTARS
PORTLAND CEMENT
HYDRATED LIME
AGGREGATE
WATER
BLENDED HYDRAULIC CEMENTS
SLAG FROM BLAST FURNACES
MASONRY CEMENTS
BRANDS OF
PORTLAND CEMENT
BLENDED HYDRAULIC CEMENT
PLASTICIZERS
ADMIXTURES
TYPES OF MORTAR FROM HIGHEST STRENGTH TO LOWEST STRENGTH
WE WANT MORTARS THAT ARE STRONG BUT ONLY THE MINIMUM STRENGTH NEEDED FOR THAT PARTICULAR USE BECAUSE THE STRONGER THE MORTAR THE HARDER IT IS TO WORK WITH
TYPE M: HIGHEST STRENGTH, USED FOR BELOW GRADE, OR HIGH LATERAL LOADS, CLIMATES WITH HIGH FROST
TYPE S: EXTERIOR REINFORCED MASONRY, EXTERIOR LOAD-BEARING MASONRY. VENEERS SUBJECT TO HIGH WIND LOADS
TYPE N: BALANCE OF WORKABILITY AND STRENGTH, NON-LOADBEARING VENEERS AND CHIMNEYS, INTERIOR LOAD-BEARING WALLS
TYPE O: LOW STRENGTH, INTERIOR NON-LOAD BEARING
TYPE K: WEAKEST YET, NOT USED MUCH, NOT USED ANYMORE
THINK: MaSoN wOrK
HOW LONG AFTER MORTAR IS MIXED DOES THE MASON HAVE TO WORK WITH IT BEFORE IT MUST BE DISCARDED AND A NEW BATCH MIXED?
2.5 HRS
USUALLY CURES IN 1.5 HR OR SO BUT WE CAN ADD WATER TO BUY US ANOTHER HR, BUT AFTER 2.5 HRS IT WILL NEED TO BE DISCARDED FOR A NEW BATCH
WHAT CAUSES STAINING ON MASONRY WALLS?
EFFLORESCENCE
TO AVOID IT, WE WOULD NEED AN AIR CAVITY BEHIND THE MASONRY WALL FOR WATER TO HIT THAT DRAINAGE PLAIN AND DROP DOWN IT AND OUT THE WEEPS AT THE BOTTOM
BUT IF THERE ARE NO WEEP HOLES, THE MOISTURE IS SUCKED THROUGH THE MORTAR, IT PICKS UP THE SALTS THROUGH THE MORTAR, AND WITHOUT THERE BEING ANY WEEP HOLES TO COME OUT OF, ON A DRY DAY, IT GETS PULLED BACK OUT THROUGH THE MORTAR PICKING UP MORE SALT, AND DRIPS DOWN THE EDGE OF THE BUILDING LEAVING STREAKS/STAINS
BRICK
MEANT TO BE HELD AT THE SCALE OF A HAND AND READ AT SMALL SCALE
FLY ASH BRICK
ADVANTAGES
BYPRODUCT OF COAL BOILERS THAT HAS TO BE DEALT WITH ANYWAYS
STEAM CURED INSTEAD OF FIRED
USES ONLY 15% OF ENERGY NEEDED FOR CLAY BRICK WHILE HAVING THE SAME STRENGTH AND APPEARANCE
STIFF MUD PROCESS OF MAKING BRICK VS WATER STRUCK BRICK
STUFF MUD
LEAST EXPENSIVE
MOST BRICKS ARE THIS TYPE
15% WATER
RUN THROUGH VACUUM TO EXTRACT AIR POCKETS
CUT WITH WIRE
LEAST LABOR INTENSIVE
MOST HOMOGENEOUS
WATER STRUCK BRICK
SOFT MUD PROCESS 20%-30% WATER
PRESSED INTO WOOD MOLDS (BY HAND OR MACHINE)
MOLDS DIPPED IN WATER SO THAT CLAY WON'T ADHERE TO MOLD
HOW CUSTOM BRICKS ARE MADE
FOR FIRING
BRICKS GO INTO KILN
PROCESS TAKES 2 DAYS - A WEEK
PERIODIC KILN
BRICKS PUT INTO KILN, FIRED, THEN EMPTIED
TUNNEL KILN
CONTINUOUS TRAIN OF BRICKS ON RAIL CARS THAT MOVE THROUGH A TUBE
CLAMP OF BRICKS
STACKS OF BRICKS, RIGHT AT THE SITE THAT WERE BURNED
BRICKS ON THE OUTSIDE THAT WERE BURNT BUT NOT DISTORTED, THOSE WERE USED ON EXTERIOR
BADLY BURNED BUT DISTORTED WERE USED IN APPLICATIONS WHERE THEY WOULDN’T BE SEEN
IF SEVERELY UNDERCOOKED, THOSE BRICKS WERE THROWN OUT ALTOGETHER
BRICK STANDARD SIZE(S)
THERE REALLY IS NO ‘STANDARD’ BUT
‘MODULAR’ IS MOST COMMON: 3-⅝” x 2-¼” x 7-⅝”
OTHER SIZES ARE CALLED: STANDARD, KING, UTILITY, NORMAN, ROMAN
COST
UTILITY BRICK WALL IS LESS EXPENSIVE, THEY ARE BIGGER BRICKS AND NEED LESS MORTAR
WILL COST 75% OF MODULAR BRICK WALL AND WILL RESIST MORE COMPRESSIVE LOADS
WHICH BRICK MORTAR JOINTS ARE ACCEPTABLE FOR OUTDOOR USE WHERE IT RAINS AND/OR FREEZES?
CONCAVE JOINT AND VEE JOINT
STANDARD BRICK MORTAR HEIGHT
⅜” IS KNOWN AS STANDARD BUT IN REALITY WILL BE BETWEEN ¼” TO ½”
BRICK TYPES TO BE FAMILIAR WITH
COPING BRICK
JAMB BRICK
SILL BRICK
ANGLE BRICK
RADIAL BRICKS
BRICKS WITH HOLES IN THEM
CORED BRICK (CONSISTS OF 3 HOLES IN IT BUT CONSIDERED SOLID)
HOLLOW BRICK (USED FOR REINFORCING BARS THEN FILLED WITH GROUT
FROGGED BRICK (CONSISTS OF 1 RECT SUPPRESSION IN IT BUT CONSIDERED SOLID)
IF 75% SOLID OR GREATER IS CONSIDERED SOLID
IF YOU WANT TO A TRULY SOLID BRICK YOU HAVE TO SPECIFIC UNFROGGED, UNCORED, 100% SOLID BRICK
HOLLOW BRICK IS ANYTHING THAT IS AT LEAST 40% SOLID
WHICH IS USED FOR BRICK APPLICATIONS THAT ARE VISIBLE, FACING BRICK OR BUILDING BRICK?
FACING BRICK AS IT LOOKS BETTER, COULD BE STRUCTURAL OR NON-STRUCTURAL
BUILDING BRICK APPEARANCE DOES NOT MATTER, CAN BE USED AS BACKUP WIDTH
FOR MULTI WIDTH WALL, DISTANCES BETWEEN THE TWO BRICK WALLS ARE
MIN ⅜”
MAX 4”
GROUT VS CONCRETE
EACH MADE OF PORTLAND CEMENT, AGGREGATE, AND WATER
GROUT IS MORE FLUID, MORE POURABLE
LOW LIFT VS HIGH LIFT GROUTING
IF WE ARE GOING TO GROUT A LOT AT A TIME, IT PUTS A LOT OF HYDROSTATIC PRESSURE ON THE BRICK
LOW LIFT GROUTING POURED IN 4 FOOT COURSES AT A TIME
HIGH LIFT GROUTING CONSISTS OF A TALLER REINFORCED WALL, SOME BRICKS INTENTIONALLY OMITTED, THEN INSERTED INTO THE CAVATIES LATER ON
MOST COMMON APPEARANCE FRADE FOR FACING BRICK
FBA FACING BRICK - MORE VARIATION IN SIZE AND CHIPPAGE
FBS FACING BRICK - SOME VARIATION IN SIZE AND CHIPPAGE (LESS MACHINED LOOK IS PREFERRED)
FBX FACING BRICK - MORE DIMENSIONALLY UNIFORM AND LESS CHIPPAGE
MNEMONIC TRICK TO REMEMBER: ‘A’ = ANOMALY; ‘S’ = STANDARD; ‘X’ =XACTING
WHICH GRADE OF BRICK IS MOST APPROPRIATE FOR USE BELOW GRADE?
MW WEATHER RESISTANT, USED ON EXTERIORS, BUT ONLY IN WARM AREAS (NEGLIGIBLE WEATHERING)
NW ONLY FOR INTERIOR
SW USED FOR UNDERGROUND, ACCEPTABLE FOR ANY CLIMATE AND BELOW GRADE, MOST HARDIEST
MNEMONIC TRICK TO REMEMBER: ‘MW’ =MIAMI BRICK; ‘NW’ = NTERIOR BRICK; ‘SW’ = SNOW BRICK
BRICK ORIENTATIONS
BRICKS TURNED 90 DEGREES (AKA HEADERS) TIE THE TWO ROWS OF BRICKS (AKA STRETCHERS) TOGETHER
BRICK PATTERNS
VERTICAL OPTIONS SEEN ON ELEVATIONS IE WALLS
RUNNING BOND
FLEMISH BOND
COMMON BOND
ENGLISH BOND
HORIZONTAL OPTIONS
SEEN ON FLOORS IE PAVERS
HERRINGBONE
**********#21-#35 MISSING **********
LEWIS PINS
USED FOR LIFTING STONE
SOME STONES HAVE RESIDUE OF WHERE LEWIS PINS WENT INT
STRAP ANCHORS
ANCHOR MORTAR TO WALL
METHODS OF STONE ANCHORING
DONE AT THE SEAMS, WITH EITHER MORTAR OR SOMETHING ELSE
BUILD UP OPTIONS AS SUCH
FLASHING / BACK UP WALL OF CMU WITH ADJUSTABLE BRACKETS / STRAP ANCHORS
FLASHING / BACK UP WALL OF CMU WITH ADJUSTABLE BRACKETS / Z-TIES
FLASHING / BACK UP WALL OF CMU WITH ADJUSTABLE BRACKETS / THREE-WIRE TRUSS TIE
STEEL COLUMN WITH ANCHOR ATTACHED THAT TIE INTO THE CMU
FLASHING / BACK UP WALL OF CMU WITH ADJUSTABLE BRACKETS / LADDER LOOP TIES
CONCRETE BACKUP WALL WITH VERTICAL TRACKS CASTED INTO IT THAT HAVE ADJUSTABLE HEIGHT DOVETAIL ANCHORS
SHEATHING MEMBER / CORRUGATED TIES / MASONRY
FLASHING / BACK UP WALL OF CMU WITH ADJUSTABLE BRACKETS / ADJUSTABLE TIES
FLASHING / BACK UP WALL OF CMU WITH ADJUSTABLE ADJUSTABLE STONE TIES
TEXT $$$$$
ENCLOSURE
BUILDING ENCLOSURE HAS TO PROVIDE THE FOLLOWING:
SUPPORT
RAIN CONTROL
AIRFLOW CONTROL
THERMAL CONTROL
VAPOR CONTROL
CONTINUITY IS KEY FOR WATER CONTROL LAYER
CONTINUOUS FROM FLOOR TO WALL TO ROOF
FULLY ADHERE PRODUCTS PERFORM BETTER FOR RAIN CONTROL THAN LOOSE SHEETS, NO SHIT
HOW DO WE MEASURE AIR TIGHTNESS IN A BUILDING, WHAT EQUIPMENT DO WE USE, AND WHAT METRICS DO WE USE?
BLOWER DOOR
USED TO MEASURE HOW MANY CUBIC FEET PER MINUTE LEAVE THE BUILDING
WE HAVE BEEN MOVING TOWARDS MEASURING CUBIC FEET PER MINUTE, PER SQUARE FOOT OF SKIN AREA
ON AIR CONTROL
WE WANT BUILDINGS TO BE AIRTIGHT, THE AIR THAT DOES COME IN, SHOULD BE INTENTIONAL AND CONTROLLED
WE WANT AIR TO COME IN FROM THE WINDOWS, OPERABLE SKYLIGHTS, OPERABLE DOORS, MECH SYSTEM, ETC, BUT NOT FROM THE SKIN
IF IT IS NOT AIRTIGHT THEN MOISTURE WILL COME IN AS WELL
WHY DON'T WE WANT AIR MOVING IN AND OUT OF THE BUILDING?
HEAT FLOWS OUT
MOISTURE CAN BE TRAPPED ON THE INSIDE
CAN CAUSE COLD DRAFTS OR COLD SURFACES INSIDE
IN SUMMERS, OPPOSITIE WITH COLD AIR FLOWING OUT
MOISTURE IS BROUGHT INSIDE
CONDENSATION MAY CAUSE MOLD OR ROT
WHAT CAUSES MEMBRANE FLUTTERING?
WIND CAUSING MEMBRANES TO FLAP AND EVENTUALLY GET UNDONE
AIR BARRIER TIGHTNESS
TARGET CFM/SF SKIN @ 75 PASCALS
BARRIER: <0.004 CFM/SF SKIN
OPAQUE SKIN ASSEMBLY: <0.04 CFM/SF SKIN
BUILDING: <0.4 CFM/SF SKIN
WHAT IS MORE IMPORTANT WHEN DESIGNING AN AIR BARRIER THE SHEETS OR THE SEAMS BETWEEN THE SHEETS?
THE SEAMS BETWEEN THE SHEETS
7.3 $$$$$
WHICH OFFERS HIGHER INSULATION VALUES, MATERIALS WITH HIGH U-VALUES OR MATERIALS WITH HIGH R-VALUES?
MATERIALS WITH HIGH R-VALUES ALWAYS OUTPERFORM IN CONDUCTIVE HEAT LOSSES THOSE WITH U-VALUES
R-VALUES AND U-VALUES ARE OPPOSITE, SO WHEN R-VALUES GO UP, U-VALUES GO DOWN
INSULATION OUTBOARD OF THE BUILDING STRUCTURE IS LESS LIKELY TO HAVE THERMAL BRIDGING COMPARED TO THOSE IN CAVITIES TUCKED BETWEEN STRUCTURAL ELEMENTS
DIFFERENT TYPES OF INSULATION TO GET FAMILIAR WITH
EXPANDED POLYSTYRENE (EPS)
EXTRUDED POLYSTYRENE (XPS)
FACED POLYISOCYANURATE (POLYISO)
CLOSED-CELL SPRAY FOAM
OPEN-CELL SPRAY FOAM
GLASS FIBER (FIBERGLASS)
MINERAL WOOL (ROCKWOOL)
WHICH INSULATION MATERIAL HAS A HIGHER EMBODIED ENERGY CELLULOSE OR EXPANDED POLYSTYRENE?
EXPANDED POLYSTYRENE
MATERIALS THAT HAVE A PETROCHEMICAL ELEMENT TO THEM HAVE MUCH HIGHER EMBODIED ENERGY
FOR HIGH PERFORMANCE BUILDINGS, WHICH PORTION OF THE WALLS SHOULD HAVE WINDOWS?
AS A GENERAL RULE OF THUMB, LESS THAN 35% WINDOWS
A VAPOR CONTROL LAYER IS INTENDED TO PREVENT VAPOR DRIVEN MOISTURE FROM PASSING THROUGH OR TO ALLOW VAPOR DRIVEN MOISTURE TO PASS THROUGH?
A BIT OF A TRICK QUESTION AS WE WANT IT TO KIND OF DO BOTH, WE WANT IT TO THROTTLE, BUT MORE IMPORTANTLY LET SOME OF IT PASS THROUGH
THE GOAL IS TO LIMIT THE AMOUNT OF MOISTURE FROM COMING THROUGH, AND MAKING SURE THAT THE WATER IMPERMEABLE LAYER IS FAIRLY WARM IN THE WINTER AND ABLE TO SHED MOISTURE LIKE RAIN
IF THERE IS CONDENSATION WE WOULD WANT THAT WATER IMPERMEABLE LAYER TO DRY BOTH WAYS
HOW DO YOU ATTACH EXT CLADDING TO RIGID INSTALLATION?
A LOT OF TIMES WITH CLIPS DIRECTLY FROM THE BUILDING STRUCTURE THROUGH THE INSULATION TO CLADDING
WE CAN USE VERTICAL FURRING STRIPS INSTEAD UP AGAINST THE RIGID INSULATION AS A COMPRESSIVE STRUT, WHICH ALSO ALLOWS FOR A CAPILLARY CAVITY FOR RAIN TO RUN DOWN
IF YOU USE TWO VAPOR BARRIERS
THEN MOISTURE WILL GET IN BUT NOT BE ABLE TO EVER GET OUT
IE LIKE A WATER BOTTLE LEFT ON A LAWN OR IN A CAR FOR DAYS AND DAYS, NEVER DRIES OUT, STILL HAS DROPLETS OF WATER INSIDE
WHICH ALLOWS LESS MOISTURE TO PASS? CLASS 1, CLASS 2, OR CLASS 3 VAPOR RETARDANT
CLASS 1
WHICH IS MORE LIKELY TO ALLOW FOR CONDENSATION AIR INFILTRATION OR VAPOR DIFFUSION?
AIR INFILTRATION
BECAUSE MOISTURE COMES THROUGH ON A MICROSCOPIC LEVEL AND SOME ALSO COMES THROUGH IN THE AIR
AREAS WITH COOLING LOADS, WINDOWS SHOULD BE SHADED
19.3 $$$$$
WHERE SHOULD YOU LOCATE EA OF THE LAYERS IN A WALL ASSEMBLY?
DEPENDS ON MANY THINGS IE WHAT KIND OF BUILDING, IN WHICH CLIMATE ZONE, ETC
BUT IF WE ARE TALKING ABOUT AN ABOVE GROUND FRAMED WALL, AND WE ARE GOING TO PUT THE FIBROUS INSULATION IN THE CAVITIES BETWEEN THE STUDS HOW IT IS USUALLY DONE, SUCH AS GLASS FIBER OR MINERAL WOOL, WE KNOW THAT WE DO NOT WANT CONDENSATION ON THE INSIDE OF THE EXTERIOR SHEATHING IN WINTER
WE HAVE TO LOOK AT OUR CLIMATE ZONE AND ACCOUNT FOR THE FOLLOWING
IF WE ARE IN CLIMATE ZONE 1, 2, 3, 4A OR 4B WE CAN GET AWAY WITH NO VAPOR CONTROL LAYER, NONE IS REQUIRED
IF WE ARE IN CLIMATE ZONE 4C, 5, 6, 7 OR 8, WE DO NEED A VAPOR CONTROL LAYER, WE NEED TO PUT IT ON THE INSIDE OF THE INSULATION BECAUSE IT IS COLD MOST OF THE TIME, AND WE ARE GOING TO USE THAT TO LIMIT THE VAPOR DIFFUSION GOING INTO THE WALL
AS A GENERAL RULE, YOU WANT TO PLACE THE VAPOR BARRIER ON
WARM SIDE OF THE INSULATION IE FOR
ALASKA (SLAM DUNK COLD CLIMATE):
EXT CLADDING | CAPILLARY BREAK | INSULATION AKA THERMAL CONTROL | VAPOR BARRIER | SHEATHING | STRUCTURE | INT FINISH
MIAMI (SLAM DUNK WARM CLIMATE):
EXT CLADDING | CAPILLARY BREAK | VAPOR BARRIER | INSULATION AKA THERMAL CONTROL | SHEATHING | STRUCTURE | INT FINISH
STRUCTURES
LONG SLENDER COLUMN SUPPORTS A PORTION OF ROOF, MANY OTHER COLUMNS 20’ APART, WHAT WOULD DICTATE THE DIAMETER OF THE COLUMN?
BUCKLING IN THE COLUMN
INTERNAL FORCES IN A COLUMN, IE COMPRESSION, BUT IN THIS CASE, THAT IS NOT GOING TO BE THE GOVERNING FACTOR
COMPRESSION IS WHEN YOU HAVE A BIG LOAD FROM ON TOP
BUT IN THIS CASE IT IS KIND OF LIKE A GIANT TOOTHPICK
WHAT GOVERNS THE SIZING OF THE COLUMN IS NOT THE WEIGHT ABOVE BUT THE FACT THAT IT IS LONG AND SKINNY/SLENDER
WHICH COLUMN IS MOST LIKELY TO BUCKLE?
PINNED - PINNED
MOMENT - FREE
MOMENT - MOMENT
THERE ARE DIFFERENT WAYS TO BRACE A COLUMN IR:
ROTATION FIXED AND TRANSLATION FIXED: MOMENT
ROTATION FREE AND TRANSLATION FIXED: PIN
ROTATION FIXED AND TRANSLATION FREE: (SLIDES IN ONE DIRECTION) (USED IN SEISMIC)
ROTATION FREE AND TRANSLATION FREE: (LIKE A FLAG POLE)
HIGHER K-VALUE
MORE LIKELY TO BUCKLE
COMPRESSION
AT THE TOP OF THE BEAM IN THE MIDDLE
TENSION
AT THE BOTTOM OF THE BEAM ALSO IN THE MIDDLE
SHEAR FORCES
WHERE COLUMN MEETS A BEAM
BENDING MOMENT
IS WHEN/WHERE BEAM WANTS TO SMILE
IN MOST CASES BEAM SIZES ARE CONTROLLED BY
BENDING MOMENT
IE WHAT IS THE MAX BENDING MOMENT BEFORE THE BEAM SPLITS AT THE BOTTOM MIDDLE?
DEFLECTION BECOMES AN ISSUE IF THERE IS VIBRATION
FOR MULTIFAMILY BUILDINGS IN WOOD, DEFLECTION SHOULD BE ONLY ¼ OF WHAT STRUCTURAL CODES SAY
FUNCTIONS OF L
SHEAR IS FUNCTION OF L
MOMENT IS FUNCTION OF L2
DEFLECTION IS FUNCTION OF L3
IF WE DOUBLE THE LENGTH
WE DOUBLE THE SHEAR
WE QUADRUPLE THE MOMENT
WE MULTIPLIED THE DEFLECTION BY A FACTOR OF 8
COST DIFFERENCES BETWEEN THE FOLLOWING
$ SHEAR WALL (WOULD BE A GOOD IDEA TO USE AT FIRE EXIST SHAFTS)
$$ BRACED FRAME
$$$ MOMENT RESISTING
WHICH IS A MORE COMMON STRUCTURAL SYSTEM, COLUMN WINS OR BEAM SPANS EVERY OTHER COLUMN?
COLUMN WINS IS MORE COMMON AND BETTER TYPICALLY
IF BEAM SPANS EVERY OTHER BEAM, THERE WILL BE TORSIONAL BUCKLING AT BEAM AND COLUMN IN THE MIDDLE OF THE BEAM
*IF BEAM SPANS SAY 7 COLUMN, THEN IT IS PROTECTED BY THE TORSIONAL BUCKLING BUT THAT IS NOT PRACTICAL IE IT IS NOT POSSIBLE TO GET A BEAM THAT LONG ON A TRUCK/TRANSPORT
1 KIP
1000 LBS
HOW TO CALC BENDING MOMENT
M = w * L² / 8 (also written as: M = wl² / 8)
M = MAX BENDING MOMENT
w = LOAD PER LINEAR FOOT
IF L = 10’ AND w = 80 lbs/ft THEN:
M = 80 * 10² / 8
M = 80 * 100 / 8
M = 8000 / 8
M = 1000 ft-lb
AGAIN/RECAP
MOMENT
HOW MUCH THE BEAM WANTS TO SMILE
SECTION MODULUS
HOW ROBUST THE GEOMETRY OF THE BEAM IS
HIGHER SECTION MODULUS
STRONGER BEAM WHICH MEANS, THE GEOMETRY IS SUCH THAT IT IS A STRONGER BEAM
HIGHER MOMENT
THERE IS MORE FORCE
IF WE DOUBLE THE MOMENT
IE MORE WEIGHT OR INCREASED THE LENGTH OF THE BEAM
THEN OBVIOUSLY THERE WILL BE MORE BENDING STRESS
LIKEWISE, IF WE DOUBLE THE SECTION MODULUS
THEY WE ARE GOING TO HAVE A LOWER MAX BENDING STRESS
***REVISIT STRUCTURES #9.3 & #10.3***
WHICH ARROWS OF LATERAL HYDROSTATIC FORCE FROM THE SOIL IS GREATER?
-----GRADE LEVEL-----
A>>>
B>>>
‘B’ BECAUSE THE WEIGHT FROM ABOVE IE WHERE ‘A’ IS INCREASES THE PRESSURE
WHAT IS A SOFT STORY PROBLEM?
A BUILDING WITH A HEAVY LOAD/ROOF ON TOP
COMMON IN MULTISTORY BUILDINGS WHERE THE GROUND FLOOR IS EITHER A PARKING GARAGE OR SOME SORT OF MIXED USE WITH BIG OPENINGS
WHEN YOU HAVE A TOP HEAVY BUILDING
IF YOU ARE NOTCHING INTO THE JOIST, WHERE CAN YOU PUT THE NOTCH?
RULES IN THE CODE FOR NOTCHES IN WOOD STRUCTURES:
IF WE HAVE A BEAM SUPPORTED ON BOTH SIDES
NOTCH ON ENDS < ¼ OF BEAM DEPTH
NOTCH ELSEWHERE ⅙ OF BEAM DEPTH
WIDTH OF NOTCH < ⅓ OF BEAM DEPTH
MIDDLE ⅓ OF BEAM IS OFF LIMITS
WE CAN PUT A HOLE ANYWHERE
HOLE’S DIAMETER < ⅓ OF BEAM DEPTH
EDGE OF HOLE HAS TO BE AT LEAST 2” FROM EITHER END OF THE JOIST
IF WE HAVE TWO HOLES
THEY NEED AT LEAST 2” BETWEEN
FOR HOLES IN STUDS
MAX DIAMETER IS 40% OF STUD DEPTH
IF A LARGER DIAMETER IS NEEDED
CAN ACHIEVE A MAX OF 60% BY DOUBLING THE STUD UP
EDGE OF HOLE
NEEDS TO BE AT LEAST 5/8” FROM EDGE OF STUD
IF NOTCHING A STUD
MAX 25% OF STUD DEPTH
CAN NOT PUT A HOLE IN THE SAME CROSS SECTION OF A NOTCH
HOW DO WE KNOW IF A BOLT IS TIGHT ENOUGH?
DIRECT TENSION INDICATOR (PIECE OF METAL SIM TO A WASHER WITH PUNCHED OUT METAL TABS THAT FLATTEN OUT AS TIGHTENED), IT IS THEN MEASURED AND TIGHTENED SOME MORE IF NECESSARY
SLIP CRITICAL BOLT CONNECTION
SQUEEZE TIGHT FOR FRICTION TO RESIST MOVEMENT
BEARING-SHEAR BOLT CONNECTION
SNUG-FIT MOVEMENT ASSUMED
SITE
WHY DO WE DIG DOWN FOR FOUNDATIONS?
TO REACH BEDROCK OR COMPETENT SOIL FOR BUILDING LOADS TO BE TRANSFERRED DOWN INTO THE GROUND
FOR PLACES THAT ACTUALLY HAVE A WINTER IT IS TO GO BELOW THE DEPTH OF FROST LINE TO AVOID AREAS OF FREEZE/THAW
WHAT ARE BUOYANT UPLOAD FORCES? (THINK BuOyAnT)
WHEN UNDERGROUND WATER PUSHES UP ON THE BUILDING AND CAUSES THE BUILDING TO FLOAT LIKE A BOAT
LOADS
DEAD LOADS: WEIGHT OF THE BUILDING THAT ARE PERMANENT
LIVE LOADS: PEOPLE AND FURNISHINGS, EVEN RAI
LATERAL LOADS: WIND AND HURRICANES AND ALSO SEISMIC
LATERAL SOIL LOADS: WEIGHT OF SOIL PUSHING UP AGAINST BASEMENT WALL
SETTLING
WE WANT BUILDINGS TO SETTLE THE SAME EVERYWHERE
CLASSIFY EARTH MATERIALS IN LARGEST TO SMALLEST PARTICLE
BOULDERS: TAKES TWO HANDS TO LIFTED UP
COBBLES: EASILY PICKED UP BY ONE HAND
GRAVEL: EASILY HELD BETWEEN TWO FINGERS
SAND: IF ONE PIECE IS TOO SMALL TO BE EASILY PICKED UP BY YOUR FINGERS, BUT LARGE ENOUGH TO SEE THE INDIVIDUAL PARTICLES
SILT: PARTICLES ARE TOO SMALL TO BE SEEN BY THE NAKED EYE, BUT WHEN VIEWED UNDER MAGNIFICATION, PARTICLES ARE SPHERICAL
CLAY: PARTICLES ALSO TOO SMALL TO BE SEEN BY NAKED EYE, WHEN VIEWED UNDER MAGNIFICATION, PARTICLES LOOK PLATE-LIKE
EXAMPLES OF ORGANIC SOILS
TOPSOIL
PEAT SOIL
NEITHER ARE GOOD FOR CONSTRUCTION BECAUSE BUILDING CAN NOT BEAR ON IT, BUT COULD BE USED FOR LANDSCAPING
CLASSIFY EARTH MATERIALS IN ORDER OF MOST TO LEAST COMPETENT FOR SUPPORTING A BUILDING
GRAVEL
SAN
SILT
CLAY
WHICH OF THE ABOVE IS THE WEIRD ONE?
CLAY: PLATE LIKE SHAPE RATHER THAN SPHERICAL, HAS ITS OWN GRAIN, BECAUSE OF THE FLAT LIKE SHAPE IT MIGHT HAVE THOUSANDS OF TIMES THE SURFACE AREA OF SILT
WHEN WET, CLAY IS PUTTY-LIKE AND STICKY AND WHEN DRY, IT IS BRITTLE
EXPANSIVE AS IN IT EXPANDS AND CONTRACTS DEPENDING ON MOISTURE
WHEN BUILDING IS BUILT ON CLAY, THE WEIGHT OF THE BUILDING CAN PUSH THE MOISTURE OUT OF IT, CAUSING IT TO COMPRESS ITS VOLUME, THAT PROCESS IS CALLED CONSOLIDATION
WHICH IS CONSIDERED FRICTIONAL AND WHICH IS CONSIDERED COHESIVE OUT OF CLAY, GRAVEL, AND SAND?
CLAY IS COHESIVE
GRAVEL AND SAND ARE FRICTIONAL
SOIL LIQUID LIMIT
LIQUID CONTENT WHEN SOIL TRANSFORMS FROM SEMI SOLID TO FLUID
SHEAR STRENGTH AS IT APPLIES TO EARTH MATERIALS
DENSELY PACKED COARSE GRAIN SOILS EXHIBIT HIGHER SHEAR STRENGTH
LOOSELY PACKED COARSE GRAINED SOILS EXHIBIT LESS SHEAR STRENGTH
SMALLER GRAINED SOILS: SAND, CLAY, SILT, HAVE AN EVEN LOWER SHEAR STRENGTH AND CAN CARRY LESS BUILDING
SOILS
WELL GRADED SOIL CONSISTS OF A WIDER VARIETY OF GRAVEL, WHERE THE SMALLER ONES FILL IN THE VOIDS OF THE BIGGER ONES, THE WHOLE THING PACKS MUCH TIGHTER, AND THIS KIND OF GEOMETRY IS BETTER FOR A BUILDING BEARING ON IT
WELL GRADED = POORLY SORTED (GOOD FOR SUPPORT)
POORLY GRADED SOIL NOT AS GOOD FOR SUPPORT BUT DRAINS BETTER THAN WELL GRADED SOIL
POORLY GRADED = WELL SORTED (BETTER FOR DRAINAGE)
WATER TABLE
ELEVATION AT WHICH THE SOIL IS WATER SATURATED AND CANT HOLD ANYMORE WATER
BROWNFIELD SITE
A CONTAMINATED SITE OR A SITE THAT IS BELIEVED TO BE CONTAMINATED, ESPECIALLY PLACES THAT WERE DISPOSAL SITES FOR CHEMICALS, OR SITES THAT HAD UNDERGROUND STORAGE FOR FUELS LIKE GAS STATIONS, OR PAINT FACTORIES, ETC
GRUBBING AND CLEARING
TAKING OUT TREES, PLANTS, AND STUMPS WITH HEAVY MACHINERY
ANGLE OF REPOSE
STEEPEST ANGLE THAT THE SIDE OF THE EXCAVATED AREA CAN BE BEFORE THE SOIL BACKSLIDES INTO THE PIT
IT CAN BE STEEP FOR COHESIVE SOILS, TYPICALLY 45 DEGREES, CLAY MAY BE AROUND 53 DEGREES
BUT SHALLOW FOR FRICTIONAL SOILS, TYPICALLY 34 DEGREES
SNOW HAS 38 DEGREE
COFFEE BEANS AND ASHES HAVE A 40 DEGREE
BARK MULCH HAS A 45 DEGREE ANGLE
SOLDIER BEAMS
WIDE FLANGE STEEL BEAMS THAT ARE DRIVEN INTO THE SOIL
THEN PLANKS OF WOOD CALLED LAGGING IS PLACED BETWEEN AS PART OF SHORING
FOR SHEATHING
WE CAN USE STEEL, WOOD, ALUMINUM, PLASTIC, COMPOSITE OR PRE-CAST CONCRETE
FOR TRENCHES
WE CAN UTILIZE REUSABLE MODULAR SYSTEMS
SOILS MIXING
CREATE WALLS FOR EXCAVATION BEFORE WE START DIGGING BY DRILLING DOWN AND MIXING THE SOIL IN COLUMNS WITH CEMENT AND WATER, THEN WE CAN DIG OUT THE EXCAVATION IN BETWEEN WITH THE DRILLED COLUMNS HOLDING THE EARTH BACK
SLURRY WALL - WHAT IS IT, AND WHAT IS THE PROCESS OF MAKING IT?
A PIECE OF HEAVY MACHINERY (CLAM BUCKET) IS USED TO DIG DOWN ALL AROUND THE PERIMETER OF THE SITE, AND AS WE DIG, THE SIDES OF OUR WALL WANT TO COLLAPSE IN ON US, SO WE KEEP THEM OUT BY KEEPING A HEAVY MIXTURE OF CLAY AND WATER WHICH IS THE ‘SLURRY’ THAT CREATES HYDROSTATIC PRESSURE OUTWARD THAT WILL KEEP THE EARTH FROM SLIDING IN, THEN WE ARE GOING TO MAKE A CONCRETE WALL OUT OF IT BY PUTTING A REINFORCING (RABAR) INTO THE HOLE AND USING A GIANT FUNNEL TO POUR CONCRETE TO BE DISPLACED INTO THE SLURRY, THIS PROCESS IS DONE IN BARRIERS (SEGMENTS) BECAUSE WE CAN NOT POUR THE WHOLE WALL AT ONE TIME, BUT THEN THAT WALL IS USED ALLOW US TO EXCAVATE ONE SIDE OF IT, WE PUT STRUCTURAL MEASURES TO KEEP THE WALL BACK, WE CAN BEGIN TO OCCUPY THE SPACE AND PUT OUR FOUNDATION DOWN
TRENE
A GIANT FUNNEL FOR IE CONCRETE
WHAT IS THE DIFFERENCE BETWEEN CROSSLOT BRACING AND RAKERS?
CROSSLOT BRACING GOES ALL THE WAY ACROSS THE EXCAVATION, IE FROM ONE EXCAVATION WALL HORIZONTALLY ACROSS ALL THE WAY TO THE OTHER
RAKERS ONLY GO PART WAY ACROSS AND TERMINATE AT THE EARTH, IE FROM THE SIDE OF THE EXCAVATED WALL DOWN TO THE BOTTOM OF THE EARTH AT AN ANGLE LIKE A KICKSTAND
HOW ARE TIEBACKS HELD INTO THE EARTH?
GIANT RODS USED TO HOLD THE EXCAVATION WALL BACK IF THE SOIL ON THE OTHER SIDE IS COMPETENT, TIED INTO EARTH USING GROUT,
HORIZONTAL MEMBERS ARE WALERS, AND A HYDRAULIC JACK IS USED TO PULL IT TIGHT, ONCE THE FLOOR(S) IS PLACED, THEY DO THE WORK OF KEEPING THE WALLS STABILIZED IN HOLDING THE EARTH BACK
HOW CAN YOU KEEP OUT WATER OF AN EXCAVATION THAT IS DUG LOWER THAN THE WATER TABLE?
OPTION 1: BUILD A WATERPROOF ENCLOSURE AROUND THE EXCAVATED EARTH SO THAT WATER CAN NOT GET IN AKA ‘BUILD A BATHTUB’
OPTION 2: CONTINUE TO PUMP THE WATER OUT OF THE EXCAVATION
OPTION 3: CONTINUE TO PUMP THE WATER OUT OF THE AREA AROUND THE EXCAVATION SO THAT THE WATER DOES NOT EVEN GET IN
FOUNDATIONS/STRUCTURES
A LARGE BUILDING NEEDS DEEP FOUNDATION
PART ABOVE GROUND IS CALLED SUPER STRUCTURE
PART BELOW GROUND IS CALLED SUBSTRUCTURE
BELOW ANY OF THE SPACES THAT TRANSFERS THE LOAD TO THE EARTH IS CALLED FOUNDATION
HOW DO WE DECIDE WHAT KIND OF FOUNDATION TO USE?
IF A SHALLOW FOUNDATION IS FEASIBLE, IF BUILDING IS SMALL ENOUGH, AND THE SOIL IS COMPETENT THAN WE CAN GO WITH A SHALLOW FOUNDATION
COLDER CLIMATE FOUNDATIONS
DEEPER BECAUSE OF FROST DEPTH
SO THE GROUND TEMPERATURE IS STABLE ENOUGH TO AVOID FREEZE/THAW
SPREAD FOOTINGS
USED FOR SHALLOW FOUNDATIONS
WALL FOOTING: FOUNDATION WALL BEARS DOWN ON THE FOOTING AND IT WILL BE A LINEAR LOAD
COLUMN FOOTING: FOR A POINT LOAD IE A COLUMN
***IF YOU NEED TO BRACE COLUMN FOOTINGS TO ONE ANOTHER FOR LATERAL SUPPORT FOR THE WHOLE SYSTEM TO STAY RIGID WE WILL USE A GRADE BEAM***
HORIZONTAL BEAM ON GRADE
SLAB ON GRADE
LOW LOADS, DON'T HAVE TO WORRY ABOUT FROST
COMBINED FOOTING
SIMILAR TO COLUMN FOOTING BUT ARE A VERSION OF COLUMN FOOTINGS THAT STRETCH/CONNECT TO ONE ANOTHER
CANTILEVER FOOTING
USED WHEN STRUCTURE IS UP AGAINST A PROPERTY LINE
MAT FOUNDATION
SO MANY COLUMNS THAT ARE CLOSE TOGETHER SO IT HAS ONE FOOTING FOR ALL OF THEM AT THE BOTTOM
GRADE BEAM VS TIE BEAM
THEY BOTH TIE COLUMNS TOGETHER AT GRADE BUT TIE BEAMS ONLY TACKLE HORIZONTAL LOADS, GRADE BEAMS HANDLE BRACE LOAD AND THEIR OWN VERTICAL LOADS AS WELL
SHALLOW FROST PROTECTED FOOTING
INSULATION THAT RUNS ALONG EXTERIOR WALL DOWN INTO THE EARTH AND OUT AWAY FROM THE BUILDING, THIS WAY WE DON’T HAVE TO WORRY ABOUT FREEZING AT/NEAR THE BUILDING
FLOATING FOUNDATION
VARIATION OF MAT FOUNDATION, NEEDED TO CALC THE WEIGHT OF THE BUILDING AND WEIGHT OF SOIL ON SITE THAT WE ARE REMOVING AND MAKE THEM BE EQUAL
REMOVING THE SAME AMOUNT OF SOIL IN WEIGHT AS WE ARE ADDING IN BUILDING AND BY DOING THAT WE HAVE NOT REALLY ADDED ANYTHING FROM A SOIL POINT OF VIEW
WHAT DO WE DO TO FOUNDATIONS FOR EARTHQUAKES
RUBBER DAMPERS
HYDRAULIC SHOCK ABSORBERS
BASE ISOLATION PADS
CAISSONS VS PILES
CAISSONS DRILLED AND THEN FILLED W CONCRETE
PILES ARE HAMMERED INTO THE GROUND
HOW CAN YOU IMPROVE THE FOUNDATION OF AN EXISTING BUILDING AS PART OF A RENOVATION/EXPANSION?
UNDERPINNING
WHICH IS ESSENTIALLY THE RENOVATION OF THE UNDERGROUND PORTION
3 REASONS TO UNDERPIN
IF BUILDING IS HEAVIER THAN IT WAS MADE TO BE WHEN FOUNDATION ORIGINALLY POURED
IF EXISTING FOUNDATION WAS NEVER SUFFICIENT AND NEEDS TO BE IMPROVED
ADJACENT SITEWORK WEAKEN THE FOUNDATION
3 WAYS TO IMPROVE
EXTEND THE FOUNDATION TO SOME DEEPER STRATA WITH MORE COMPETENT SUPPORT
MAKE THE FOUNDATION WIDER SO THAT IT RESTS ON MORE SOIL
IMPROVE THE EARTH WITH IMPORTED FILL OR GROUT
HOW TO KEEP BASEMENTS DRY
DRAINAGE
WATERPROOFING
5 STEPS TO KEEP BASEMENTS DRY
WELL MAINTAINED GUTTERS, ROOF DRAINS, DOWNSPOUTS
SOME PLACE TO DISCHARGE ROOF WATER AWAY AND DOWNHILL OF THE BUILDING
SLOPED SITE AWAY FROM THE BUILDING TO BRING SURFACE RAINWATER AWAY
A BREAK IN THE SOIL SO THAT WATER THAT WOULD OTHERWISE PRESS AGAINST THE FOUNDATION WALL WILL INSTEAD DROP
A PERFORATED PIPE TO ACCEPT THE WATER TO CARRY IT AWAY
HOW TO PROVIDE THE CAPILLARY BREAK IN THE SOIL?
DRAINAGE MAT
GRAVEL
HOW DO YOU PROVIDE WATERPROOFING?
SHEETS
LIQUID-APPLIED BARRIER
SPECIAL CONCRETES
WATERPROOFING
SURFACE TREATED TO RESIST THE PASSAGE OF WATER UNDER HYDROSTATIC PRESSURE
DAMP PROOFING
DESIGNED TO RESIST THE PASSAGE OF WATER ONLY IN THE ABSENCE OF HYDROSTATIC PRESSURE
INTEGRAL WATERPROOFING
MIXED INTO CONCRETE TO MAKE CONCRETE LESS LIKELY TO LEAK WATER
FILLING VS BACKFILLING
BACKFILLING IS A SUBSET OF FILLING
BACKFILLING: REPLACING SOIL THAT HAD ONCE BEEN REMOVED FROM THE SITE
FILLING: ADDED IN LAYERS KNOWN AS ‘LIFTS’ IN 4” LAYERS WHICH MAY NEED COMPACTION FOR STABILITY
RETAINING WALL VS BASEMENT WALL
RETAINING WALLS KEEP EARTH BACK, TYPICALLY EXTERIOR AND EARTH IS ON ONE SIDE AND NOT THE OTHER
ALTA SURVEY VS TOPOGRAPHICAL SURVEY
ALTA: EASEMENTS AND RIGHT OF WAYS AND LAND IMPROVEMENTS
TOPO: MEASURING CONTOURS OF THE LAND
TOPO FEATURES TO BE ABLE TO SKETCH/KNOW/UNDERSTAND
PEAK
VALLEY
CLIFF
BERM
SWALE
COFFERDAM VS CHECK DAM
COFFERDAM IS A TEMPORARY STRUCTURE USED TO KEEP OUT A BODY OF WATER
CHECK DAM IS USED AT A STEEP SLOPE TO SLOW DOWN THE WATER IN THE EVENT OF A HEAVY RAIN TO AVOID MUDSLIDES AND/OR CORROSION
RIPRAP
ROCK USED TO PROTECT THE SHORELINE OR ANY PLACE WHERE WATER MEETS THE LAND AND HELPS PREVENT EROSION
WAYS TO PREVENT EROSION
USE RIPRAP ALONG SHORELINE
REPLANT VEGETATION SUITED TO SITE CONDITIONS
FOOTPATHS WITH EXPOSED SOIL, COVER IN MULCH OR GRAVEL
USE STEPPED TERRACES
BUILD CHECK DAMS
REDIRECT AND CAPTURE RUNOFF
ZONING ORDINANCE VS VARIANCE
ZONING ORDINANCE: RULES
ESTABLISHES DENSITY, ALLOWABLE USES, PARKING REQUIREMENTS, SETBACKS
VARIANCE: EXCEPTION TO THE RULE(S)
RIGHT OF WAY VS EASEMENT
RIGHT OF WAY ALLOWS SOMEONE TO PASS THROUGH
EASEMENT IS SO THAT OTHER PARTIES CAN USE THE LAND FOR UTILITIES IE WIRES AND PIPES
WHAT IS THE MOST IMPORTANT FACTOR FOR LOCATING A NEW SHOPPING CENTER?
ACCESSIBILITY TO MARKET AREA TRAFFIC
SINCE CONTAMINATION IN SOIL TYPICALLY LEADS TO GROUNDWATER CONTAMINATION, WHICH OF THE FOLLOWING CLEANUP TECHNOLOGIES CAN BE USED TO REMEDIATE THE UNSATURATED ZONE?
VAPOR EXTRACTION
DRILL EXTRACTION WELLS TO SUCK GAS OUT OF THE SOIL AND WITH THAT WE SUCK POLLUTANTS OUT FOR TREATMENT ABOVE GROUND
THE FOLLOWING SITE CONDITIONS AFFECTS THE DEVELOPMENT POTENTIAL OF A PARCEL OF LAND
WETLANDS
ENDANGERED SPECIES
HAZARDOUS WASTE
EXISTING INFRASTRUCTURE
SOLAR GEOMETRY
SOLAR NOON: WHEN THE SUN IS DIRECTLY ABOVE YOU REGARDLESS OF IF IT IS REALLY NOON
SUMMER TIME 23.5 DEGREES NORTH OF THE EQUATOR (WHICH IS THE FURTHEST SUN GOES FROM THE EQUATOR)
TROPIC OF CANCER
SUMMER TIME ADD 23.5 DEGREES TO (90 DEGREES MINUS LATITUDE)
WINTER TIME 23.5 DEGREES SOUTH OF THE EQUATOR
TROPIC OF CAPRICORN
WINTER TIME SUBTRACT 23.5 DEGREES FROM (90 DEGREES MINUS LATITUDE)
FALL AND SPRING
VERNAL EQUINOX: MARCH 21
AUTUMNAL EQUINOX: SEPTEMBER 21
FALL AND SPRING TIMES ONLY CALCULATE 90 DEGREES MINUS LATITUDE
ONE ACRE
43,560 SQUARE FEET
ONCE A FIRE IS DETECTED
THE ELEVATOR GOES ON FIRE SERVICE MODE
ELEVATORS CAN NOT BE ACCESSED BY THE PUBLIC
ELEVATORS AUTOMATICALLY RETURN TO THE FIRST FLOOR AND THE DOORS REMAIN OPEN (FIRST FLOOR OR FLOOR OF EGRESS)
IF SMOKE DETECTED ON THAT FLOOR THERE IS A PREPROGRAMMED ALTERNATE FLOOR
THE ELEVATOR CAN MANUALLY BE ACTIVATED BY THE FIREFIGHTER EVEN DURING A FIRE USING A KEY
TREES ASSOCIATED WITH WIND BREAKS
CONIFEROUS
SINCE THEY NEVER LOSE THEIR LEAVES
TREES ASSOCIATED WITH SHADING
DECIDUOUS
GOOD FOR SHADING IN THE SUMMERS AND ALLOW LIGHT TO COME IN DURING WINTER TIME TO HELP HEAT AS THEY LOSE THEIR LEAVES SEASONALLY
----
SYSTEMS BONUS
TEXT$$$$$
CODES
RAMPS
MAX CROSS SLOPE OF ADA RAMP 1:48 OR 2%
ADA RAMP RUN: 1:12 EVERY 30’ WITH 5’ LANDING
LANDING NEEDED AT THE BOTTOM AND TOP OF RAMP OF MIN 5’ EACH IN THE DIRECTION OF TRAVEL
***YOU CAN HAVE A SLOPE OF 1:20 WHICH YOU DO NOT NEED LANDINGS NOR RAILINGS FOR, CONSIDERED SITE FEATURE***
60”x60” LANDING WHERE PEOPLE ARE TURNING 90 DEGREES OR EVEN 180 DEGREES
RAMP CAN BE LESS THAN 60” IE 48” MIN, BUT LANDING ITSELF STILL NEEDS TO BE 60”x60”
CURB CUT WIDTH
48” MIN
FIRE LANES
NEEDED WHEN 150’ OF FIRE HOSE IS NOT ENOUGH TO REACH THE BACK OF A BUILDING
WIDTH: 20’ ACROSS
MUST BE 10’ AWAY FROM OVERHANG
TURNING RADIUS
OUTSIDE: 54’
INSIDE: 30’
CARRY MIN OF 35 TONS
EGRESS
PRINCIPLE OF BROOKS AND STREAMS AND RIVERS
ALTERNATE PATHS REQUIRED
DEAD END CORRIDORS
SHOULD BE LIMITED TO 20’ IF UNSPRINKLERED
50’ IF SPRINKLERED
IN SOME CASES CAN BE LONGER IF YOU HAVE A WIDE WIDTH OR A CERTAIN OCCUPANCY
OCCUPANCY GROUP 1-3 CONDITION 2, 3, OR 4
DEAD END = 50’ OR MORE
1BC 408.6 - SMOKE COMPARTMENTALIZATION
1BC 903.2.6 - AUTOMATIC FIRE SPRINKLERS
OCCUPANCY B, E, F-?, M, R-1, R-2, S, U
DEAD END = 50’ OR MORE
IBC 903.3.1.1 - (NFPA 13) AUTOMATIC FIRE SPRINKLERS
CORRIDOR MUST BE LESS THAN 2.5 TIMES THE CORRIDOR WIDTH
IF ELEV CORRIDOR IS 10’ (10’ x 2.5 = 25’)
LESS THAN 25’ WOULD BE ACCEPTABLE
EXIT REQUIREMENTS
49 PEOPLE OR LESS: 1 EXIT
50 PEOPLE OR MORE: 2 EXISTS
MIN REQ DIMENSION IS ½ THE LONGEST DIAGONAL DIMENSION OF THE SPACE
EGRESS DIVIDED INTO 3 MAIN SEGMENTS: ACCESS, EXIT, DISCHARGE
ACCESS: PORTION FROM GIVEN PART OF BUILDING TO THE FIRE STAIR, MOST REMOTE POINT IN THE SPACE TO THE EXIT WHICH IS THE FIRE STAIR, MAX DISTANCE DETERMINED BY CODE BOOK
EXIT: DOORS THAT AUTO CLOSE INTO FIRE STAIR, OR STAY OPEN MOST OF THE TIME AND CLOSE ONLY WHEN FIRE TO FIRE STAIR
DISCHARGE: THE OUTLET/DOOR TO THE EXTERIOR
EXITS
IF EXIT IS MORE THAN 75’ ABOVE GRADE, AND/OR IF YOU HAVE AN UNDERGROUND BUILDING
EXIT NEEDS TO BE PRESSURIZED W A FAN
ALL INTERIOR STAIRWAYS HAVE TO BE CLOSED W FIRE SEPARATION
4 OR MORE STORIES: 2HR RATING
LESS THAN 4 STORIES: 1HR RATING
ACCESS ROUTES MIN WIDTH
44” MIN IF OCCUPANCY OF 49 PEOPLE OR MORE
36” MIN IF OCCUPANCY OF LESS THAN 49 PEOPLE
CEILING HEIGHT
MIN IS 7’-0”, CAN GO DOWN TO 6’-8” BUT FOR NO MORE THAN HALF OF THE SPACE
WIDTH OF STAIR
UNSPRINKLERED BUILDING: OCCUPANTS SERVED BY FLOOR x 0.3 = MIN WIDTH
SPRINKLERED BUILDING: OCCUPANTS SERVED BY FLOOR x 0.2 = MIN WIDTH
WIDTH OF HALLWAYS IN ACCESS
DOOR CAN ONLY PROTRUDE INTO EXIT ACCESS CORRIDOR CAN NOT BLOCK MORE THAN HALF OF THE WIDTH
WHEN DOOR FULLY OPEN DOOR CAN NOT PROTRUDE MORE THAN 7” INTO THE HALLWAY
GUARDRAILS
SO YOU DO NOT FALL OVER
42” TYPICALLY (34” TO 38” IN RESIDENTIAL)
GUARD SPACING CAN NOT BE MORE THAN 4”
HANDRAILS
SO YOU CAN GRAB ONTO SOMETHING
34” TO 38” FROM NOSING ON STAIR TREAD
TOP OF HANDRAIL NEEDS TO EXTEND 12” HORIZONTALLY THEN RETURN INTO THE WALL
IF AT CORRIDOR, NEEDS TO TURN THE CORNER AND EXTEND 12” THEN TURN INTO THE WALL
BOTTOM OF HANDRAIL AT LANDING NEEDS TO EXTEND THE DEPTH OF A STAIR TREAD DIAGONALLY AND THEN EXTEND 12” HORIZONTALLY THEN RETURN INTO THE WALL
HANDRAIL PROJECTION
4.5” MAX OFF THE WALL
1.5” MIN CLEARANCE BETWEEN HANDRAIL AND ADJACENT SURFACE/WALL
HANDRAIL DIAMETER
1.25” MIN
2” MAX
FOR EXIT STAIR, WIDTH OF STAIR IS MEASURED
BETWEEN HANDRAILS
SMOKE BAFFLES
OFTEN MADE OF GLASS ARE FOUND AT THE TOP OF EA FLOOR AT/OF AN ATRIUM SPACES SO THAT IF/WHEN SMOKE BUILDS UP, IT IS KEPT THERE TO SLOW DOWN THE SPREADING OF IT UPWARDS TO THE OTHER FLOORS
AREA OF REFUGE
30” x 48”
FOR ADA, PERSON IN WHEELCHAIR, TO ACCESS EXIT WHERE MORE PROTECTED WHERE A FIREMAN CAN REACH YOU AND BE OUT OF THE WAY OF OTHERS EXITING THE BUILDING
ZONING
LOCAL IE COUNTY/CITY/TOWN, BASED ON FAR, SETBACKS, MAX HEIGHTS
TABLE 503 ALLOWABLE BUILDING HEIGHTS AND ASSEMBLIES
FAMILIARIZE YOURSELF WITH IT
BUILDING TYPES
TYPE I: CONCRETE CONSTRUCTION
TYPE II: CONCRETE CONSTRUCTION
TYPE III: STEEL & CONCRETE
TYPE IV: HEAVY TIMBER (VERY RARELY USED)
TYPE V: LIGHT WOOD CONSTRUCTION
THOSE HAVE A & B WITHIN THEM (EXCEPT TYPE IV)
EFFECT FLOOR AREA AND BUILDING HEIGHT AND ALSO BUILDING MATERIALS
MAINLY TWO CATEGORIES
LESS COMBUSTIBLE VS MORE COMBUSTIBLE
TYPE I-A AND TYPE I-B
NON COMBUSTIBLE AND FIRE RESISTIVE
TYPE I-A
HAS HIGHER FIRE RESISTANCE THAN I-B
IE IF I-B HAS NO RATING OR 1 HR RATING, TYPE I-A MAY REQUIRE A 2HR RATING, AND THOUGH MORE STRINGENT RULE FOR ‘A’, IT CAN ALLOW TO BUILD A BIGGER/TALLER BUILDING
TYPE II-A AND TYPE II-B ARE NON COMBUSTIBLE (GENERALLY) BUT THEY ARE NOT REALLY FIRE RESISTIVE
SO YOU CAN’T BUILD WITH THINGS THAT BURN, BUT YOU HAVE MUCH LESS REQUIREMENT FOR FIRE RESISTANCE
TYPE II-A
MIN 1 HR RATING THROUGHOUT
TYPE II-B
NON COMBUSTIBLE (GENERALLY) AND DOES NOT REQUIRE FIRE RATING MINIMUM
TYPE III-A AND TYPE III-B
GENERALLY COMBUSTIBLE AND HAVE NO EXTRA FIRE RESISTANCE, IE WOOD FRAMING
TYPE III-A
NEEDS FIRE RESISTANCE THROUGHOUT AND 2 HR FIRE RATING ON EXTERIOR BEARING WALLS W 1 HR RATING INTERIOR BEARING WALLS
TYPE III-B
1 HR FIRE RATING ON EXTERIOR WALLS AND NO FIRE RATING ON INTERIOR WALLS
TYPE IV
HEAVY TIMBER
TYPE V-A AND TYPE V-B
COMBUSTIBLE CONSTRUCTION AND LESS FIRE RESISTANCE THAN TYPE III
TYPE V-A
NEEDS 1 HR FIRE RATING ON EXTERIOR BEARING WALLS AND NO FIRE RATING ON INTERIOR BEARING WALLS
TYPE V-B NO FIRE RATING REQUIRED
OCCUPANCY
PER SIZE OF BUILDING AND PROGRAM, WE ARE GOING TO DIVIDE THAT BY A NUMBER FROM A TABLE AND WE ARE GOING TO FIND OUT HOW MANY PEOPLE WE CAN HAVE IN EACH OF THESE AREAS.
1004.1.2 MAX FLOOR AREA ALLOWANCES PER OCCUPANT
IBC TABLE 2902.1
FAMILIARIZE YOURSELF WITH THIS TABLE
LOCATE OCCUPANCY CLASSIFICATION
IE A-3
IE FOR EVERY 200 MALES WE NEED 1 SINK
SO SAY WE HAVE 750 MALES (750 / 200 = 3.7 AND SO WE ROUND UP TO 4)
IBC TABLE 601 FIRE-RESISTANCE RATING REQUIREMENTS
FAMILIARIZE YOURSELF WITH THIS TABLE
IBC TABLE 508.4 REQUIRED SEPARATION OF OCCUPANCIES (HOURS)
FAMILIARIZE YOURSELF WITH THIS TABLE
OCCUPANCIES ON LEFT COLUMN AND OCCUPANCIES ON TOP ROW
JUST IGNORE THE DASHES: ‘-’
S = SPRINIKLERED
NS= NOT SPRINKLERED
N = NO SEPARATION REQUIRED
NP = NOT PERMITTED, IE WE CAN'T HAVE GASOLINE STORED NEXT TO A HOSPITAL
IBC TABLE 602 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXT WALLS BASED ON FIRE SEPARATION
FAMILIARIZE YOURSELF WITH THIS TABLE
BASED ON DISTANCE, TYPE OF CONSTRUCTION AND ASSEMBLY GROUP
CERTAIN FIRE RATING REQUIREMENTS TO PREVENT FIRES, ETC OF ENTIRE NEIGHBORHOODS/BLOCKS BURNING DOWN
WHICH 2 TYPES OF CONSTRUCTION ARE CONSIDERED NON COMBUSTIBLE ALLOWING FOR BIGGER BUILDINGS BUT MORE RESTRICTIONS ON USAGE OF MATERIALS?
TYPE I AND TYPE II (GENERALLY CONCRETE BUILDINGS)
WHICH CONSTRUCTION TYPE CONSISTS OF NONCOMBUSTIBLE EXTERIOR WALLS AND INTERIOR BUILDING ELEMENTS OF ANY MATERIAL ALLOWED BY THE CODE?
TYPE III
WHICH KIND OF PRIMARY STRUCTURE WOULD BE USED FOR CONSTRUCTION TYPE II-B?
EXPOSED STEEL COLUMN
TYPE II-A REQUIRES A 1 HR RATING AROUND THE STRUCTURAL COLUMN, BUT TYPE II-B REQUIRES NO RATING (GENERALLY THE A’S REQUIRE MORE OF A FIRE RATING THAN THE B’S)
FOR EGRESS STAIR
DOORS SHOULD ALWAYS SWING IN THE DIRECTION OF EGRESS TRAVEL
REGULATORY ELEMENTS
CORRELATE WITH THE APPROPRIATE GOVERNMENTAL LEVEL IE NATIONAL, STATE, AND LOCAL (SEE BELOW)
NATIONAL
AMERICANS WITH DISABILITIES ACT
FAIR HOUSING ACT
STATE
ARCHITECTURAL LICENSE
BUILDING CODE
LOCAL: ZONING ORDINANCE
MASTER PLAN
HISTORIC OVERLAYS
COVENANTS
UNSPRINKLERED BUILDING MAX CORRIDOR LENGTH CAN BE HOW MUCH?
20’
A SUITE THAT NEEDS 2 EXITS IS BECAUSE IT EXCEEDS THE NUMBER OF HOW MANY OCCUPANTS?
49 PER TABLE 1015.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY
NUMBER OF EXITS PER OCCUPANT LOAD
0-49 PEOPLE = 1 EXIT
50-500 PEOPLE = 2 EXITS
501-1000 PEOPLE = 3 EXITS
OVER 1000 PEOPLE = 4 EXITS
WHAT IS THE REQUIRED CLEAR FLOOR SPACE FOR AN INDIVIDUAL WITH A DISABILITY PER ICC A117.1-2009 AS FAR AS THE LENGTH AND WIDTH?
48” x 30”
STANDARD PULL SIDE FRONT APPROACH PER ICC A117.1
60” MIN OFFSET FROM THE FRONT ORIGINATING FROM THE SWING SIDE OF DOOR
18” MIN OFF TO THE SIDE FROM FRONT OF DOOR PULL
HOW MANY TOTAL OCCUPANTS CAN A STAIR WITH A WIDTH OF 3’-8”
44” / 0.3 = 146.67 (IN THIS CASE WE NEED TO ROUND DOWN TO 146 PEOPLE)
WE DIVIDE BY 0.3 PER 1005.3.1 OF IBC FOR NON SPRINKLERED BUILDING
ORDER OF TASKS
1. OCCUPANCY CLASSIFICATION
HELPS DETERMINE OCCUPANCY COUNT (PER CODE HOW MANY PEOPLE BUILDING CAN HANDLE)
HELPS DETERMINE NUMBER OF EXITS, EXIT WIDTHS, NUMBER OF TOILETS, ETC
2. HEIGHT AND AREA LIMITATIONS
CONCRETE (GENERALLY TYPE I-A/B OR TYPE II-A/B)
STEEL (GENERALLY TYPE III-A/B)
WOOD (GENERALLY TYPE V A/B)
3. CONSTRUCTION TYPE
IF WE CAN’T MEET THE REQUIRED SQ FOOTAGE AFTER RUNNING THROUGH THESE STEPS/NUMBERS WE MIGHT CIRCLE BACK AND HAVE TO CHANGE THE BUILDING TYPE TO ALLOW FOR A LARGER BUILDING
OCCUPANCY TYPES
ASSEMBLIES GROUP - A
A-1
THEATERS, CONCERT HALLS, CINEMAS
MORE STRICT OCCUPANCY CLASSIFICATION
TYPICALLY DARK, LOTS OF PEOPLE, DANGEROUS PERFORMANCE
A-2
BANQUET HALLS, RESTAURANTS, CAFETERIAS, ETC
LESS STRICT
A-3
IE BOWLING ALLEYS, COURTROOMS, FUNERAL PARLORS, LIBRARIES
NOT SO MANY PEOPLE
NOT AS DANGEROUS
A-4
ARENAS, TENNIS COURTS, SWIMMING POOLS
A-5
OUTDOOR STADIUM
LOTS OF PEOPLE, BUT OUTSIDE
BUSINESS GROUP - B
OFFICES, BANKS, CAR WASHES, POST OFFICES, TELEVISION STATIONS, COLLEGES/UNIVERSITIES CLASSROOMS OVER 50 OCCUPANTS
NOT STORES OR PLACES WHERE PEOPLE GATHERED THAT DON’T KNOW THEIR WAY AROUND
NOT A LOT OF HAZARDOUS MATERIALS/EQUIPMENT
EDUCATIONAL GROUP - E
SIX OR MORE PEOPLE FROM DAYCARE TO 12TH GRADE
SMALL DAYCARES LESS THAN 5 PEOPLE CAN BE CLASSIFIED UNDER THE RESIDENTIAL GROUP R-3
NOT A COLLEGE LECTURE HALL
FACTORY GROUP - F
BROKEN UP INTO SEVERAL DIFFERENT CATEGORIES
GROUP F IS FOR MODERATE HAZARD MANUFACTURING
IF IT IS NOT ON THE LIST, YOU WILL NEED TO CONTACT A CODE OFFICIAL
F - 1 (MODERATE HAZARD GROUP)
MANUFACTURING BICYCLE, BOATS, ELECTRONICS, PLASTIC, OR WOODWORKING
F-2 (NON COMBUSTIBLE MATERIALS GROUP)
MANUFACTURING PACKAGING, METALS, BRICKS, BEVERAGES, ETC
HIGH HAZARD GROUP - H
PROCESS THAT COULD HARMFUL TO HEALTH
COMBUSTIBLE DUST, EXPLOSIVES, UNSTABLE CHEMICALS, MANUFACTURING SEMICONDUCTORS, CORROSIVE MATERIALS, ETC
HAS DIFFERENT LEVELS: H - 1, H - 2, H - 3, H - 4, H - 5
DOES NOT HAVE TO BE MANUFACTURING
INSTITUTIONAL GROUP - I
I - 1
ASSISTED LIVING AND GROUP HOMES
I - 2
HOSPITALS AND NURSING HOMES
MORE STRINGENT RULES IN THE CODE
PLACES WHERE SOME PEOPLE MAY BE IMMOBILE OR LESS MOBILE THAN I-1 OCCUPANTS
I - 3
JAILS AND PRISONS
***IF GROUP - I IS 5 OR FEWER PEOPLE, IT CAN BE CLASSIFIED AS RESIDENTIAL IF IT IS SPRINKLERED***
MERCANTILE GROUP - M
RETAIL, MARKETS, DRUG STORES
RESIDENTIAL GROUP - R
R - 1 = VERY STRINGENT
HOTELS, TRANSIENT, TEMPORARY PLACES
A LOT OF PEOPLE WHO PROBABLY DO NOT KNOW WHERE TO GO DURING AN EMERGENCY
R - 2
APARTMENTS, DORMITORIES, FRATERNITIES, SORORITIES, OTHER NON-TRANSIENT MULTIFAMILY
STILL A LOT OF PEOPLE, BUT THEY KNOW WHERE TO GO IN AN EMERGENCY
R - 3 = NOT SO STRINGENT
SINGLE FAMILY HOUSE OR DUPLEXES
HALFWAY HOUSES, ASSISTED LIVING FACILITIES, DAYCARES
AGAIN, IF OVER 5 PEOPLE, IF NOT, CONSIDERED R - 3
IF MORE THAN 5 BUT LESS THAN 16 PEOPLE IN A 24 HOUR HALFWAY HOUSE, ASSISTED LIVING FACILITY, OR DAYCARE THEN IT CAN BE CONSIDERED R - 4
STORAGE GROUP - S
FOR STORAGE ROOMS THAT ARE BIGGER THAN 100 SF
IF LESS THAN 100 SF IT IS CONSIDERED TO BE THE OCCUPANCY OF THE SPACE IT IS IN
IF YOUR STORAGE IS MORE THAN 100 SF THERE MAY BE EXTRA RULES IN THE CODE YOU HAVE TO ABIDE BY
S - 1
MODERATE HAZARDS STORAGE
AEROSOLS, SHOES, MATTRESSES, SUGAR, ETC
S - 2
LOW HAZARD STORAGE
FRUIT, VEGETABLES, BAGGED CEMENT, METALS, ETC
UTILITY GROUP - U
UTILITY AND MISC. BUILDINGS
BARNS, CARPORTS, GREENHOUSES, SHEDS, ETC
FIRE SEPARATION
FOR A 2 HR WALL, THE PENETRATION ALSO NEEDS TO HAVE A 2 HR RATING
IF 1 HR WALL, NEEDS I HR FIRE BLOCKING (FIRE BLOCKING IE WOOD OR SOME SORT OF OTHER BARRIER)
IF 2 HR WALL, NEEDS TO HAVE 2 HR FIRE STOP (FIRESTOP IS A GUE THAT YOU PUT IN AT THE PENETRATION)
TYPE - 1 BUILDING
MUST HAVE AN EXTERIOR WALL THAT IS NON COMBUSTIBLE.
DOES THE BALCONY THAT PROJECTS FROM THAT WALL ALSO NEED TO BE NON COMBUSTIBLE?
YES, IT DOES
SO DO CORNICES AND EAVE OVERHANGS AS WELL
THEY NEED TO CONFORM TO THE EXTERIOR WALL REQUIREMENTS
EXTERIOR WALLS MUST HAVE A FIRE RESISTANCE RATING TO ACCOUNT FOR FIRE EXPOSURE FROM WHICH OF THE FOLLOWING?
INSIDE ONLY?
OUTSIDE ONLY?
BOTH SIDES?
INSIDE ONLY OR BOTH SIDES
IF NEIGHBORING BUILDING HAS A FIRE SEPARATION DISTANCE THAT IS GREATER THAN 5’
INSIDE ONLY
IF NEIGHBORING BUILDING HAS A FIRE SEPARATION DISTANCE THAT IS LESS THAN 5’
BOTH SIDES
FIRE SEPARATION
DISTANCE BETWEEN YOUR BUILDING AND THE LOT LINE
OR
DISTANCE BETWEEN YOUR BUILDING AND HALF THE DISTANCE TO THE NEIGHBORING BUILDING
OR
DISTANCE BETWEEN YOUR BUILDING AND HALFWAY ACROSS THE STREET
PARAPETS ARE REQUIRED
WHERE THE EXTERIOR WALL IS REQUIRED TO BE FIRE RESISTANT RATED
ZONING VS LIFE SAFETY
YOU HAVE TO GO WITH THE CODE THAT IS MOST STRINGENT
FIRE SPRINKLERS
CAN BE SET OFF ACCIDENTALLY IF THE BULB THAT KEEPS WATER BACK MELTS SAY IF IT GETS TOO HOT VIA HEAT GAIN THROUGH A SKYLIGHT OR IF IT IS TOO CLOSE TO A HEATER THAT IS CONSTANTLY BLOWING HEAT AT IT TO WHERE IT GETS IT TO BE OVER 160 DEGREES
HIGH TEMPERATURE SPRINKLERS AVAILABLE FOR SPRINKLERS THAT ARE CLOSE TO A SKYLIGHT OR A HEATER
TO AVOID THE OPPOSITE PROBLEM OF FREEZING, YOU WANT TO USE A DRY PIPE WHICH USES AIR AT THE BEGINNING OF THE PIPE INSTEAD OF WATER SO THAT THE WATER IN THE PIPE DOES NOT FREEZE AND BLOCK THE WATER FLOW FOR WHEN IT NEEDS TO SPRAY. THE FIRST FEW SECONDS WILL BE BLOWING OUT AIR, BUT THE WATER WILL FOLLOW SHORTLY THEREAFTER
FIRE SEPARATION
NO SEPARATION NEEDED BETWEEN THE SAME SET OF OCCUPANCY
2 HR RATED WALL NEEDS HOW MANY LAYERS OF GYP BOARD ON EA SIDE?
2 LAYERS ON EA SIDE
GENERALLY SPEAKING
1 LAYER ON EA SIDE = 1 HR RATED WALL
2 LAYER ON EA SIDE = 2 HR RATED WALL
3 LAYER ON EA SIDE = 3 HR RATED WALL
TYPE X GYPSUM BOARD
⅝” THICK AND IT HAS A DENSER CORE WITH GLASS FIBERS
DOES MAX CORRIDOR LENGTH INCREASE IN SPRINKLERED BUILDINGS?
YES
SPRINKLERED: 200’
NON SPRINKLERED: 150’
MAY A NON COMBUSTIBLE BUILDING USE VINYL FLOORING?
YES, IF THE VINYL FLOOR ITSELF IS FIRE RATED
ARE ARCHITECTS RESPONSIBLE FOR ENSURING THAT FIRE SEPARATION IS MAINTAINED?
YES, NOT ONLY FOR DESIGN, BUT SOMETIMES FOR CONSTRUCTION AS WELL
WHEN RENOVATING A HISTORIC BUILDING, WHERE IS THERE MORE FLEXIBILITY, IN THE ACCESSIBILITY CODE OR THE FIRE CODE?
FIRE CODE! FIRE CODE! FIRE CODE!
WHY DO SKYSCRAPERS STEP BACK AS THEY GO UP?
EXTERIOR WALL SEPARATION DISTANCE AS FIRE SEPARATION RULES ONLY TAKE EFFECT IN CERTAIN SITUATIONS AFTER FLOOR ‘X’
WHICH IS BEST PRACTICE IN A FIRE, TO PRESSURIZE A BUILDING OR TO EXHAUST A BUILDING?
BOTH!
CODE HACKS
50 OR MORE PEOPLE TRIGGERS REQUIREMENT FOR SECOND EGRESS
300 PEOPLE IN A BUILDING TRIGGERS THE REQUIREMENT FOR A CENTRAL FIRE ALARM SYSTEM, SAFE AREAS, BACKUP GENERATOR
A SECOND FLOOR TRIGGERS A REQUIREMENT FOR MULTIPLE STAIRS AND AN ELEVATOR
IF YOUR BUILDING HAS ANY OF THESE SPACES THEY ARE A TRIGGER: RESTAURANT, GYM, ASSEMBLY SPACE, TRANSIENT OR TEMPORARY RESIDENTIAL IE A HOTEL, STORAGE ROOMS OVER 100 SF
IF BUILDING REQUIRES STANDPIPE SYSTEMS, IT WILL BE MORE EXPENSIVE
16 UNITS OR MORE IN A RESIDENTIAL BUILDING
CHANGE OF USE IN AN EXISTING BUILDING THAT REQUIRES A CHANGE OF OCCUPANCY
ESPECIALLY FOR PRESERVATION CASES
WILL REQUIRE A LOT OF REVIEWS EVEN IF THE CHANGE IS RELATIVELY SMALL
GREEDY OR INTRANSIGENT NEIGHBOR
TYPES OF REPAIRS/ALTERATIONS
REPAIRS
PATCHING, RESTORING/REPLACING DAMAGED MATERIALS OR FIXTURE
TRYING TO MAINTAIN THE COMPONENTS IN GOOD CONDITION
LEVEL 1 ALTERATIONS
REMOVING, REPLACING, OR COVERING SOMETHING WITH A NEW MATERIAL, EQUIPMENT, OR FIXTURE
THE NEW MATERIAL, EQUIPMENT, OR FIXTURE SERVES THE SAME PURPOSE
LEVEL 2 ALTERATIONS
RECONFIGURING THE SPACE
ADDING OR REMOVING AN ELEMENT FROM A SPACE
EXTENDING, RECONFIGURING, OR INSTALLING A NEW SYSTEM
LEVEL 3 ALTERATIONS
WHEN THE WORK EXCEEDS MORE THAN 50% OF THE BUILDING AREA
YOU WILL NEED TO WORK WITH A CODE OFFICIAL TO DECIDE WHAT LEVEL RENOVATION A PROJECT WILL BE BECAUSE OF THE OVERLAPS BETWEEN LEVELS
WHICH CONSTRUCTION TYPE CONSISTS OF NONCOMBUSTIBLE EXTERIOR WALLS AND INTERIOR BUILDING ELEMENTS OF ANY MATERIAL ALLOWED BY THE CODE?
TYPE III
PROFESSIONAL PRACTICE
A WARRANTY
POSES THE MOST RISK FOR THE ARCHITECT IF MENTIONED IN THE CONTRACT
PHRASES IN A CONTRACT BY AN OWNER THAT MAY VOID COVERAGE BY ARCH’S INSURANCE
AS REQUIRED
AS NECESSARY
HOLD HARMLESS
INDEMNIFICATION
TAIL INSURANCE
INSURANCE THAT COVERS YOU ONCE YOU HAVE RETIRED
CONDOS AND RESIDENTIAL PROJECTS POSE THE MOST RISK
HIGH EXPECTATIONS
HOA
ETC
CHANGE TO DRAWINGS AFTER GONE OUT TO BID BUT BEFORE CONTRACTOR SELECTED
ADDENDUM
THE FOLLOWING FOUR TYPICALLY CONTRACT WITH THE ARCHITECT DIRECTLY
CIVIL ENGINEER
LANDSCAPE CONSULTANT
LIGHTING CONSULTANT
MECH/PLUMBING ENGINEER
THE FOLLOWING FOUR TYPICALLY CONTRACT WITH THE ARCHITECT DIRECTLY
A/V CONSULTANT
CODE CONSULTANT
LIGHTING CONSULTANT
COST ESTIMATOR
OWNER RESPONSIBLE FOR
SITE, SURVEY, PERMITTING, AND COMPLIANCE
RESPONSIBILITIES OF A GEOTECHNICAL ENGINEER AND NOT RESPONSIBILITIES OF CIVIL ENGINEER
SUBSURFACE SOIL ANALYSIS
AIA DOCUMENT B101 (OWNER-ARCHITECT AGREEMENT)
AUTOMOTIVE LIABILITY INSURANCE
RISK FROM AUTOMOBILE ACCIDENTS, BIGGEST RISK AN OFFICE HAS
LIABILITY EXTENDS FROM OWNERS CAR TO EVEN TAXI
GENERAL LIABILITY INSURANCE
BASIC INSURANCE THAT COVERS PROPERTY DAMAGE INJURY CLAIMS AGAINST THE FIRM
PROFESSIONAL LIABILITY INSURANCE
ERRORS AND OMISSIONS INSURANCE
PROTECTS AGAINST SOMEONE CLAIMING YOU DIDN'T DO YOUR JOB RIGHT
WORKERS COMPENSATION
COVERS SOMEBODY GETTING INJURED ON THE JOB
PROVIDES WAGE REPLACEMENT AND MEDICAL COVERAGE
IN EXCHANGE THE WORKER CANNOT SUE THE OFFICE
EMPLOYMENT PRACTICE LIABILITY INSURANCE
PROTECTS YOUR FIRM FROM A WRONGFUL TERMINATION SUIT
IE IF SOMEONE IS CLAIMING YOU FIRED THEM IN A WRONGFUL WAY
PORTION OF INSURANCE YOU NEED TO PAY
DEDUCTIBLE
ARCHITECT IS RESPONSIBLE FOR
REVIEWING THE CONTRACTOR'S INVOICES TO THE OWNER
BEFORE BID PHASE, OWNER CHANGES SOMETHING
ARCHITECT SHOULD REDESIGN BUT CHARGE THE OWNER MORE FOR THE ADDITIONAL DESIGN SERVICES
AFTER BUILDING IS BUILT, WHO OWNS THE DRAWINGS AND SPECS?
THE ARCHITECT
GIVING THE OWNER AND THE CONTRACTOR A LIMITED LICENSE TO BUILD THE BUILDING
IF OWNER USES DRAWINGS FOR A RESTAURANT AND WANTS TO BUILD MORE OF THE SAME AS A CHAIN, ARCHITECT NEEDS TO CHARGE FOR THE OTHER IE 99 RESTAURANTS THAT OWNER WANTS TO BUILD
WHEN CAN AN OWNER GET RIGHTS TO THE DRAWING EVEN WHEN THE ARCHITECT DOES NOT WANT TO GIVE THEM?
WHEN ARCH IS TERMINATED FOR CAUSE, IE WHEN ARCH DID SOMETHING WRONG, OWNER CAN FIRE THE ARCHITECT AND STILL USE DRAWINGS
15.3
EXTRA SERVICES LIST
FAMILIARIZE YOURSELF WITH IT
FAMILIARIZE YOURSELF WITH THE FOLLOWING
CIRCULATION AREA
GROSS AREA
TOTAL MEASURED TO EXTERIOR FACE
NET AREA
RENTABLE AREA
USABLE AREA
FLOOR AREA RATIO OF A FIVE-STORY BUILDING WITH A 20,000 SF BUILDING ON A 100,000 SF LOT
1.0
GROSSING FACTOR
RENTABLE AREA / USABLE AREA
19 - 28
EXERCISES ON HOURLY RATE, UTILIZATION RATE, ETC
DESIGN BID BUILD
ARCHITECT < OWNER > CONTRACTOR
OWNER CONTRACTS WITH THE ARCHITECT AND OWNER ALSO CONTRACTS WITH CONTRACTOR
CONSTRUCTION MANAGER AS ADVISOR
CONSTRUCTION MANAGER
^
ARCHITECT < OWNER > CONTRACTOR
OWNER CONTRACTS WITH THE ARCH, OWNER CONTRACTS WITH CONT, AND OWNER ALSO CONTRACTS W A CONSTRUCTION MANAGER
CONSTRUCTION MANAGER CAN WORK W ARCH ON THINGS LIKE COST, CONSTRUCTABILITY, ETC
CONSTRUCTION MANAGER IS MANAGING THE PROJECT BUT NOT FROM AN ADMINISTRATIVE POINT OF VIEW, HE IS NOT ENGAGING IN CONTRACTS WITH THE ARCHITECT
CONSTRUCTION MANAGER AS AGENT
OWNER
^
ARCHITECT < CONSTRUCTION MANAGER > CONTRACTOR
OWNER CONTRACTS WITH THE CM AND THE CM CONTRACTS W THE ARCH AND ALSO W THE CONTRACTOR
IN THIS CASE THE CONSTRUCTION MANAGER HAS MORE AUTHORITY BUT NOT NECESSARILY MORE RISK
CONSTRUCTION MANAGER MANAGES AND ADMINISTERS THE CONTRACTS
RFI’S GO THROUGH THE CM
CONSTRUCTION MANAGER AS CONSTRUCTOR
ARCHITECT < OWNER > CONSTRUCTION MANAGER
OWNER CONTRACTS WITH THE ARCH, AND OWNER ALSO CONTRACTS WITH CONTRACTOR
CONSTRUCTION MANAGER INSTEAD OF ADMINISTERING IT, ACTUALLY BUILDS IT, BUMPING OUT THE CONTRACTOR
DESIGN-BUILD
OWNER > (ARCHITECT + CONSTRUCTION MANAGER)
OWNER HAS ONE CONTRACT WITH CONTRACTOR AND ARCHITECT AS ONE ENTITY UNDER ONE UMBRELLA
LESS RISK
QUICKER
BRIDGED DESIGN BUILD
DESIGN ARCHITECT < OWNER > (ARCHITECT + CONSTRUCTION MANAGER)
DESIGN ARCHITECT WITH THE OWNER IN MIND
BRIDGING CONSULTANT
DESIGN ARCHITECT
INTEGRATED PROJECT DELIVERY METHOD
(ARCHITECT + OWNER + CONTRACTOR)
JOINT TOGETHER AS A SINGLE ENTITY
SHARE INFORMATION WITH EACH OTHER WITHOUT FEAR OF LITIGATION
SHARE BENEFITS AND RISKS OF THE PROJECT
USED MAINLY FOR LARGE AND COMPLEX PROJECTS RIGHT NOW
NEGOTIATED SELECT TEAM PROJECT DIFFERS FROM TRADITIONAL DESIGN BID BUILD
IN THAT FABRICATION STARTS EARLY
BRING IN CONTRACTOR EARLY WITH A PROFIT MULTIPLIER WITH OVERHEAD ALREADY ESTABLISHED
IE A SOPHISTICATED CURTAIN WALL CAN START EARLY WHILE ARCHITECT STILL FINISHING THEIR DRAWINGS
AND BETTER QUALITY IE CONTRACTOR ESTABLISHED BEFORE HAND
TYPES OF BIDS
NEGOTIATED BID: BETTER QUALITY
COMPETITIVE BID: LOWER CONSTRUCTION COSTS
INVITED BID: SPECIAL QUALIFICATIONS
HOW DOES COST PLUS FIXED FEE DIFFER FROM TRADITIONAL DESIGN BID BUILD
CONTRACTOR IS DISINCENTIVIZE FROM ALLOWING CONSTRUCTION COSTS TO BALLOON
FOR A BROWNFIELD SITE BEST TO GO WITH
COST PLUS FIXED FEE
DUE TO ALL OF THE POTENTIAL UNKNOWNS IE HAZARDOUS SOILS, ETC
COSTS WONT BALLOON
BEST FOR INEXPERIENCED OWNER WHO WANTS SOMETHING COMPLEX WITH AN AGGRESSIVE SCHEDULE
CONSTRUCTION MANAGER AS AGENT
PREDICTABLE RESTAURANT CHAIN, THE BEST OPTION WOULD BE TO GO WITH
TRADITIONAL DESIGN BID BUILD
WHICH ENTITY IS INTENDED TO BE MOST TEMPORARY
STRATEGIC ALLIANCE
A GROUP OF PEOPLE AGREEING TO GET A PROJECT AND DO A PROJECT AND ONCE THE PROJECT IS DONE FOR THEM TO DISSOLVE
GROUP OF COMPANIES IE ARCHI, CONTRACTOR, ARTIST, CONSULTANT, ETC
AGREE TO SHARE TECHNOLOGIES AND EXPERTISE
AGREEMENTS HAVE CLAUSES FOR NOT POACHING EMPLOYEES OF OTHER TEAMS, MEMBERS RECEIVING APPROP CREDIT, ETC
JOINT VENTURE
TYPICALLY INTENDED TO BE LONGER
TWO OR MORE COMPANIES GET TOGETHER AND CREATE A SEPERATE COMPANY
AFTER PROJECT IS DONE, THEY CAN CONTINUE TO GO FOR MORE PROJECTS AS THIS SEPARATE ENTITY
PARTNERSHIP
TRUE MARRIAGE
WHICH ENTITY PROVIDES SIMULTANEOUS LIABILITY PROTECTION AND AVOIDS DOUBLE TAXATION
LLC
BREAK DOWN OF BUSINESS ENTITIES
SOLE PROPRIETORSHIP
NO PROTECTION
GENERAL PARTNERSHIP
NO PROTECTION
LIMITED LIABILITY COMPANY (LLC)
LIABILITY PROTECTION/FLEXIBILITY
LIMITED LIABILITY PARTNERSHIP (LLP)
LIABILITY PROTECTION/DIFFERENT TIERS OF PARTNERS
S-CORP
SINGLE TAXATION
C-CORP
DOUBLE TAXATION
B-CORP
ALSO DOES GOOD FOR COMMUNITY, ETC
SPI (44 - 45 PRACTICE PROBLEM OF BUDGET/TIMELINE/PROJECT PROGRESS)
EARNED VALUE / PLANNED VALUE
SPI OF 1
MEANS YOU ARE RIGHT ON SCHEDULE
YOUR EARNED VALUE = YOUR PLANNED VALUE
FAIR LABOR STANDARDS ACT
ESTABLISHED MIN WAGE
ESTABLISH WHO IS MANAGEMENT
ESTABLISHES WHO IS PAID FOR OVERTIME
FORBIDS CHILD LABOR
THE DAVIS-BACON ACT
FOR PUBLIC WORKS PROJECTS
FAIR LOCAL PREVAILING WAGE SHOULD BE PAID
CAN'T BE MIN WAGE THAT IS SO LOW THAT ALL WORKERS ARE ON FOOD STAMPS, ETC
THE OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)
PROTECTS FROM HAZARDS ON THE JOB
AFFORDABLE CARE ACT
OBAMACARE
APPLIES TO ARCH FIRMS, HUMAN RESOURCES IN PARTICULAR
FIRMS FOR MORE THAN 50 PEOPLE TO PAY 95% OF HEALTH CARE INSURANCE
WHICH TYPE OF BID IS ASSOCIATED WITH THE SLOWEST CONSTRUCTION SCHEDULE
INVITED BID
PREQUALIFIED CONTRACTORS, PRESELECTED THAT THE DESIGN BID BUILD IS OPEN ONLY TOO
PHASED BID
IS USED DURING FAST TRACK CONSTRUCTION, PORTIONS OF THE CONSTRUCTION BID ON PIECEMEAL, IE A CURTAIN WALL BEING FABRICATED AHEAD OF TIME BEFORE ALL OF THE DRAWINGS ARE DONE
NEGOTIATED BID
CONTRACTOR BROUGHT ON AT THE INCEPTION OF THE PROJECT ALONG WITH THE ARCHITECT
FINAL BID BETWEEN THE CONTRACTOR AND OWNER
BETTER QUALITY BUT HIGHER COST BECAUSE THE CONTRACTOR IS WORKING WITH THE ARCHITECT IN REAL TIME
BID BONDS AND/OR PERFORMANCE BONDS
PROTECTS AN OWNER FROM A BUILDER DEFAULTING ON A CONTRACT
LATE BIDS ARE NOT ACCEPTED FOR PUBLIC PROJECTS WHERE THERE ARE SEALED BIDS
IT IS TO PREVENT CORRUPTION
SO THAT A LATE BIDDER CAN'T WAIT TO SEE WHAT THE LOWEST BID IS AND BID LESS THAN THAT
HOW LONG DOES A CONTRACTOR’S WARRANTY LAST?
1 YEAR
PER AIA DOCUMENT CONTRACTOR PROVIDES A WARRANTY
OR EVEN UNTIL STATUTE OF LIMITATION EXPIRES
A PROJECT IS LATE WHEN
SUBSTANTIAL COMPLETION COMES LATE (BUILDING IS FIT FOR ITS INTENDED USE)
IF CONTRACTOR NEEDS MORE TIME WHO PAYS FOR THAT?
IF THE CONTRACTOR IS AT FAULT, THEN HIM
IF ARCH, THEN ARCH
IF OWNER, THEN OWNER
PATH OF INVOICES TO THE OWNER
CONTRACTOR > ARCHITECT > OWNER
55
RETAINAGE
MONEY OWED TO THE CONTRACTOR BUT INTENTIONALLY NOT PAID YET
MECHANIC’S LIEN
METHOD FOR SUBCONTRACTORS TO GET PAID
CONTRACTOR SUBMITS INCORRECT SHOP DRAWINGS AND THE ARCH APPROVES THEM, WHO IS LEGALLY RESPONSIBLE?
CONTRACTOR
RESPONSIBILITIES:
ARCHITECT CONTRACTOR
INSTRUMENTS OF SERVICE SHOP DRAWINGS
CONTRACT DRAWINGS
ARCHITECTS DRAW THE INTENT OF SOMETHING BUT IE THE TYPE OF WELD THAT NEEDS TO BE DONE IS DETERMINED BY CONTRACTOR OR HIS SUBS
IF THE DESIGN CRITERIA IN THE CONTRACT DOCUMENTS ARE INADEQUATE WHO IS RESPONSIBLE?
ARCHITECT
WHO IS RESPONSIBLE FOR PROVIDING THE BUILDING OPERATOR WITH THE CHILLER OPERATIONS MANUAL?
CONTRACTOR
3 COPIES IN LOOSE LEAF BINDERS OF OPERATING MAINTENANCE DATE
POST-OCCUPANCY EVALUATION MEASURES A COMPLETED BUILDING’S EFFECTIVENESS BY
SURVEYING OCCUPANTS SATISFACTION
ZONES (PERTAINING TO AN INDIVIDUAL/PERSON) MEASURED IN RADIUS
INTIMATE SPACE +/- 1.5 FEET
PERSONAL SPACE +/- 4 FEET
SOCIAL SPACE +/- 12 FEET
__________ SPACE +/- 25 FEET
MOST FIRMS FOR PROFIT AND LOSS STATEMENTS USE
ACCRUAL BASIS ACCOUNTING
TWO DIFF BASIS OF ACCOUNTING
ACCRUAL
SORT OF LIKE A CREDIT CARD
TAKES INTO ACCOUNT FEES THAT ARE YET TO BE PAID AND HAVE NOT YET BEEN RECEIVED
CASH BASIS
MORE LIKE A DEBIT CARD
ADDED IN WHEN CALCULATING NET OPERATING REVENUE
FEES PAID BY THE CLIENT AS A MARKUP PERCENTAGE FOR PLOTTING OVER AND ABOVE THE COST OF PLOTTING INCURRED BY THE FIRM
CURRENT EARNINGS
VALUE CALCULATED AFTER TAXES ARE DEDUCTED FROM INCOME
NET PROFIT
CALCULATED BEFORE TAXES AND DISTRIBUTIONS (BONUSES OF OWNERS)
WHAT IS LEFT OVER ONCE YOU’VE PAID EVERYONE WHO WORKS FOR YOU AND ALL OF YOUR BILLS BUT BEFORE YOU PAY YOUR TAXES AND DISTRIBUTION
PROFIT TO EARNINGS RATIO
PROFIT / NET OPERATING REVENUE (WHICH IS AFTER BILLS PAID BUT BEFORE EMPLOYEES ARE PAID)
NET BILLING
FEES FOR THE ARCHITECT’S TIME, ESSENTIALLY THE CORE OF WHAT ARCH IS CHARGING FOR
PROSPECT
PROPOSAL THAT HAS MORE THAN 50% CHANCE OF BECOMING A FUTURE REVENUE-GENERATING PROJECT
SUSPECT
HAS LESS THAN 50% CHANCE OF BECOMING A PROJECT
PROFIT AND LOSS STATEMENT CONSISTS OF THE FOLLOWING
UTILIZATION RATE
IE 80%, 80% OF TIME IS BILLABLE TO CLIENT
OVERHEAD RATE
IF OVERHEAD RATE IS $10 THAN $10 PLUS HOURLY RATE = BREAK EVEN MULTI
BREAK-EVEN MULTIPLIER
(SEE ABOVE)
PROFIT-TO-EARNINGS RATIO
PROFIT/EARNINGS
IF $20 PROF / $100 EARN = 20% PTE RATION (WHICH WOULD BE KIND OF LOW)
NET REVENUE PER EMPLOYEE
SOMETHING ALONG THE LINES OF $100,000 PER EMPLOYEE FOR AN ACTUAL FIRM
AGED ACCOUNTS RECEIVABLE
AVERAGE TIME BETWEEN SENDING INVOICE AND GETTING PAID
SHOULD BE NO LONGER THAN 90 DAYS OR ELSE WE ARE ESSENTIALLY LENDING MONEY TO OUR CLIENTS FOR FREE
BALANCE SHEET
SOLVENCY (CURRENT RATIO): TOTAL CURRENT ASSETS / LIABILITIES
LIQUIDITY: ABILITY TO CONVERT ASSETS WE HAVE INTO CASH, HIGHER NUMBERS ARE BETTER, AT LEAST 1.0
CASH ON HAND + ACCOUNTS RECEIVABLE + REVENUE WE HAVE EARNED / LIABILITIES
LEVERAGE (DEBT TO EQUITY)
LIABILITIES / EQUITY (IDEALLY LESS THAN 35%)
RETURN ON EQUITY
TARGET SHOULD BE ABOUT 20% (YES, THAT IS HIGH, NEEDLESS TO SAY, MIGHT NOT BE DOABLE, HIGH RISK)
PROFORMA
BUSINESS PLAN
SINGLE LARGEST EXPENSE FOR AN ARCH FIRM
EMPLOYEE SALARIES
CONSTRUCTION CONTRACT HAS A COST PER LINEAR FOOT OF DRIVEWAY
UNIT PRICING
ALLOWANCES
WINDOW COVERINGS, LIGHT FIXTURES, FURNITURE, ETC
AMOUNT OF MONEY SET ASIDE FOR SOMETHING NOT SPECIFIED/DETERMINED YET
IE, A REFRIGERATOR THAT IS NOT AVAILABLE A YEAR LATER, ETC
73 - 74
ACCOUNTS RECEIVABLES
MONEY OWED TO A FIRM
76
EQUITY
MONEY COMPANY HAS MADE AND KEPT, ETC
ASSETS
WHAT FIRM OWNS AND CAN EASILY BE CONVERTED TO CASH
LIABILITIES
WHAT FIRM OWES CURRENTLY AND LONG TERM
EQUITY = ASSETS - LIABILITIES
TAKE WHAT YOU HAVE MINUS WHAT YOU OWE EQUALYS YOUR EQUITY IN THE BALANCE SHEET
YOU REFUSE TO BUILD A TORTURE CHAMBER, YOU ARE PRACTICING
CONTRACT BASED ETHICS
HOW DO YOU FILE AN ETHICAL COMPLAINT AGAINST AN ARCHITECT?
FILED THROUGH THE NATIONAL AIA (HAS A ETHICS COUNCIL), THEY ENFORCE AND INTERPRET
MOST COMMON ETHICAL COMPLAINTS
OTHER ARCHITECTS AND HOMEOWNERS
81 - 82
WHICH IS NOT FACTORED IN FOR LIFE CYCLE COST ANALYSIS
DESIGN FEES AS THEY ARE CONSIDERED SUNK COSTS
LIFE CYCLE COST ANALYSIS, WORKS BEST IF MULTIPLE OPTIONS THAT PERFORM ADEQUATELY BUT DIFFER IN COST TO INSTALL AND COST TO MAINTAIN
QUALITY MANAGEMENT
SETTING UP GUIDELINES AND METRICS
85 - 91
AIA DOC B101 ABLIGES ARCHITECT TO
CONSIDER ENVIRONMENTALLY RESPONSIBLE DESIGN ALTERNATIVES
DOES ARCH HAVE FIDUCIARY DUTY TO OWNER?
NO
AIA DOC B101 ABLIGES ARCHITECT TO
KEEP TO A SCHEDULE
AIA DOC B101 ABLIGES ARCHITECT TO OBTAIN ESTIMATED COST OF PROJECT AFTER
ALL PHASES: SD, DD, AND CD
KEEPING SOMEONE ON RETAINER MEANS
THEY PERFORM SERVICES ON A REGULAR BASIS FOR A FIXED FEE
ARCHITECT HAS TO ACCOUNT FOR
UTILITY SERVICES
ACCESS
ZONING CODE
GOV AUTHORITIES
AIA DOC B101 EXCUSES THE ARCHITECT FROM MISTAKES ASSOCIATED WITH
WORK DONE BY CONSULTANTS HIRED BY THE OWNER
AIA DOC B101 ABLIGES ARCHITECT TO
VISIT THE SITE 1 YEAR AFTER SUBSTANTIAL COMPLETION
GOV OWNED PUBLIC PROJECT WOULD MOST LIKELY GO WITH
COMPETITIVE BID
ARCHITECT IS RESPONSIBLE FOR
ADMINISTRATION OF CONSTRUCTION CONTRACT BID PROCESS
IE, DATE DUE, HOW IT WORKS, IF YOU HAVE QUESTIONS, YOU CAN ASK ME, THE ARCH
ARCH VS CONTRACTOR
INTENT VS MEANS AND METHODS
PER AIA B101 THE ARCH IS RESPONSIBLE FOR
RESPONDING QUICKLY TO RFI’S
ARCH HAS HOW LONG TO RESPOND TO AN RFI?
~2 WEEKS
RFI (REQUEST FOR INFORMATION)
DURING CONSTRUCTION
CONTRACTOR TO ARCH
RFP (REQUEST FOR PROPOSAL)
BEGINNING OF THE PROJECT
OWNER TO ARCH AND CONTRACTOR
RFS (REQUEST FOR SERVICES)
REGULAR, HOURLY BASIS
OWNER TO ARCHITECT
RFQ (REQUEST FOR QUALIFICATION)
PART OF RFP OR RFS
OWNER TO ARCH AND CONTRACTOR
RETAINAIGE IS PAID WHEN
SUBSTANTIAL COMPLETION IS REWARDED
PER AIA DOC B101, IF THERE IS A CONFLICT, THE SEQUENCE OF RESOLUTION IS
MEDIATION, THEN COURT SYSTEM
IF DISPUTE, FIRST MEDIATION THEN ARBITRATION, OR FIRST MEDIATION THEN COURT SYSTEM AS WHICHEVER ONE IS INDICATED IN THE CONTRACT
PER AIA DOC A101, THE INITIAL DECISION MAKER
RESOLVES DISAGREEMENTS BETWEEN OWNER AND CONTRACTOR
CAN A MECHANIC’S LIEN BE AWARDED TO AN ARCHITECT?
YES, IT CAN
CAN AN OWNER FIRE AN ARCHITECT JUST BECAUSE?
YES, BUT HAS TO PAY UP FOR EVERYTHING THE ARCH HAS DONE, PLUS OUTSIDE CONSULTANTS WHOSE CONTRACTS CAN’T BE CANCELED, PLUS ARCHITECT CAN CHARGE FOR THE PROFITS HE/SHE HAVE PLANNED ON
CAN ARCHITECT EVER TRANSFER A CONTRACT TO ANOTHER ARCHITECT?
NO
CONTRACTOR DISCOVERS THAT A COUNTER HEIGHT DOES NOT MEET ADA REQUIREMENTS, ACCORDING TO A101 AND B101, WHAT HAPPENS NOW?
ARCHITECT’S RESPONSIBILITY BUT THE CONTRACTOR AND OWNER ARE REQUIRED TO SHARE CONCERNS
CAN YOU CHANGE AN AIA DOC TO CHANGE THE CONTRACT TERMS?
YES
114 HUGE ASS LIST OF AIA CONTRACTS AND THEIR NUMBERS
(SUPPOSED TO MEMORIZE)
COST OF THE WORK INCLUDES THE FOLLOWING
CONTRACTOR’S MATERIALS
CONTRACTOR’S LABOR
CONTRACTOR’S PROFIT
CONTRACTOR’S OVERHEAD
DOES NOT INCLUDE ARCHITECT’S FEES
DOES NOT INCLUDE COST OF LAND
ACCORDING TO AIA DOC B101 CLAIMS MUST BE BROUGHT BEFORE
10 YEARS
(1YEAR US FOR WARRANTY) BUT FOR CLAIMS, IT IS TYPICALLY A STATUTE OF LIMITATIONS FOR 10 YEARS
ACCORDING TO AIA DOC B101 IF THERE IS A CLAIM, CONTRACT ALLOWS FOR
LIQUIDATED DAMAGES
DIFF BETWEEN CONSEQUENTIAL DAMAGES AND LIQUIDATED DAMAGES
LIQUIDATED DAMAGES = COST OF DELAY
CONSEQUENTIAL DAMAGES = LOSS OF BUSINESS THAT COULD HAVE OCCURRED IF U HAD MOVED INTO YOUR BUILDING
SUBMITTALS EXAMPLES
SHOP DRAWINGS
PRODUCT DATA SHEETS
PRODUCT SAMPLES
OFTEN SUBMITTED BY CONTRACTOR TO ARCHITECT FOR APPROVAL AND ARCH WILL LOOK THEM OVER
GANTT CHART
OVER 100 YEARS OLD, HENRY GANTT CAME UP WITH IT, WHO WAS A MECH ENGINEER
GRAPHICALLY SHOW THE ORDER OF THINGS, START OF THINGS, AND SEQUENCE OF THINGS
PERT CHART
FLAVOR OF GANTT CHART
ALSO INCLUDES GRAPHICALLY WHICH TASKS ARE DEPENDANT ON WHICH OTHER TASKS
ANTHROPOMETRIC PROPORTIONS
HUMAN PROPORTIONS, ORIGINATED BY THE MILITARY TO KNOW ERGONOMIC CALCULATIONS FOR PILOT SEATS, ETC
----------
The current MasterFormat® Divisions[8][9] are:
PROCUREMENT AND CONTRACTING REQUIREMENTS GROUP
Division 00 — Procurement and Contracting Requirements
SPECIFICATIONS GROUP
General Requirements Subgroup
Division 01 — General Requirements
Facility Construction Subgroup
Division 02 — Existing Conditions
Division 03 — Concrete
Division 04 — Masonry
Division 05 — Metals
Division 06 — Wood, Plastics, and Composites
Division 07 — Thermal and Moisture Protection
Division 08 — Openings
Division 09 — Finishes
Division 10 — Specialties
Division 11 — Equipment
Division 12 — Furnishings
Division 13 — Special Construction
Division 14 — Conveying Equipment
Facility Services Subgroup:
Division 21 — Fire Suppression
Division 22 — Plumbing
Division 23 — Heating, Ventilating, and Air Conditioning (HVAC)
Division 25 — Integrated Automation
Division 26 — Electrical
Division 27 — Communications
Division 28 — Electronic Safety and Security
Site and Infrastructure Subgroup:
Division 31 — Earthwork
Division 32 — Exterior Improvements
Division 33 — Utilities
Division 34 — Transportation
Division 35 — Waterway and Marine Construction
Process Equipment Subgroup:
Division 40 — Process Interconnections
Division 41 — Material Processing and Handling Equipment
Division 42 — Process Heating, Cooling, and Drying Equipment
Division 43 — Process Gas and Liquid Handling, Purification and Storage Equipment
Division 44 — Pollution and Waste Control Equipment
Division 45 — Industry-Specific Manufacturing Equipment
Division 46 — Water and Wastewater Equipment
Division 48 — Electrical Power Generation
ABBREVIATIONS/ORGANIZATIONS OF TRADES/DRAWINGS/NOTES/ETC ON CD SHEETS
DISCIPLINE DESIGNATORS
A ARCHITECTURAL
B GEOTECHNICAL
C CIVIL
D PROCESS
E ELECTRICAL
F FIRE PROTECTION
G GENERAL
H HAZARDOUS MATERIALS
I INTERIORS
L LANDSCAPE
M MECHANICAL
O OPERATIONS
P PLUMBING
Q EQUIPMENT
R RESOURCE
S STRUCTURAL
T TELECOMMUNICATIONS
V SURVEY/MAPPING
W CIVIL WORKS
X OTHER DISCIPLINES
Z CONTRACTOR/SHOP DRAWINGS
SHEET TYPE DESIGNATORS ARE
0 SCHEDULES, MASTER KEYNOTE LEGEND, GENERAL NOTES
1 PLANS
2 ELEVATIONS
3 SECTIONS
4 LARGE SCALE VIEWS
5 DETAILS
6 SCHEDULES AND DIAGRAMS
7 USER DEFINED
8 USER DEFINED
9 3D REPRESENTATIONS
KEYNOTES
ABBREVIATIONS THAT MAY BE COORDINATED W CSI MASTERFORMAT